Regulation 104, Central Electricity Authority (Measures relating to Safety and Electric Supply) Regulations, 2023.: Voltage limits
Central Electricity Authority (Measures relating to Safety and Electric Supply) Regulations, 2023. - Regulation 104
Text of regulation 104
Voltage limits
104. Voltage limits. – Electricity shall not be transmitted into a belowground mine at a voltage exceeding 11000 V
and shall not be used therein at a voltage exceeding 6600 V:
Provided that, -
(i) where hand-held portable apparatus is used, the voltage shall not exceed 125 V;
(ii) where electric lighting is used, –
(a) in belowground mines, the lighting system shall have a mid or neutral point connected with earth
and the voltage shall not exceed 125 V between phases;
(b) on the surface of a mine or in an open cast mine or oil mines or oil-fields, the voltage may be
raised to 250 V, if the neutral or the mid-point of the system is connected with earth and the voltage
between the phases does not exceed 250 V;
(iii) where portable hand-lamps are used in belowground mines and hazardous area of oil mines or oil-fields,
the voltage shall not exceed 30 V;
(iv) where any circuit is used for the remote control or electric inter-locking of apparatus, the circuit voltage
shall not exceed 30 V for below ground mine or hazardous area of oil-fields:
Provided that in hazardous areas of oil mines or oil-fields, the said voltage can be up to 250 V, if the on-
off control push-button stations or remote controls are housed in an appropriate enclosure like:
(i) Flame proof enclosure type „d‟;
(ii) Pressurised enclosure type „p‟;
(iii) Sand filled apparatus type „q‟;
(iv) Increased safety enclosure type „e‟, „n‟, and „o‟:
Provided further that the control circuit shall have suitable protection against shock hazards, and the
trippings due to faults do not adversely affect the operational safety:
Provided also that in fixed plants on surface of the mines or opencast mines, the said voltage for the
remote control or electric inter-locking may be permitted up to 250 V.
Previous and next
Questions people ask
Is regulation 104 of Central Electricity Authority (Measures relating to Safety and Electric Supply) Regulations, 2023. still in force?
No repeal of Central Electricity Authority (Measures relating to Safety and Electric Supply) Regulations, 2023. is recorded.