Regulation 87, Central Electricity Authority (Measures relating to Safety and Electric Supply) Regulations, 2023.: Leakage on conduit system
Central Electricity Authority (Measures relating to Safety and Electric Supply) Regulations, 2023. - Regulation 87
Text of regulation 87
Leakage on conduit system
87. Leakage on conduit system. – Where both the line and the return are placed within a conduit, the following
conditions shall be fulfilled in the construction and maintenance of the system, namely: –
(i) where the rails are used to form any part of the return, they shall be electrically connected at distances not
exceeding thirty metre apart, with the conduit by means of copper strips having a cross-sectional area of at least
0.40 sq. cm or by other means of equal conductivity and where the return is wholly insulated and contained
within the conduit, the latter shall be connected with earth at the generating station or substation through an
instrument suitable for the indication of any contact or partial contact of either the line or the return with the
conduit; and
(ii) the leakage current shall be ascertained daily, before or after the hours of running, when the line is fully
charged and if at any time it is found to exceed 0.6 ampere per km of single tramway track, the transmission and
use of electricity shall be suspended unless the leakage is stopped within twenty four hours.
Previous and next
Questions people ask
Is regulation 87 of Central Electricity Authority (Measures relating to Safety and Electric Supply) Regulations, 2023. still in force?
No repeal of Central Electricity Authority (Measures relating to Safety and Electric Supply) Regulations, 2023. is recorded.