LawGrids logoLAWGRIDS.ORG

Regulation 79, Central Electricity Authority (Measures relating to Safety and Electric Supply) Regulations, 2023.: Laying of cables

Central Electricity Authority (Measures relating to Safety and Electric Supply) Regulations, 2023. - Regulation 79

Text of regulation 79

Laying of cables

79. Laying of cables. – (1) No underground power cable of voltage level up to 33 kV shall be laid without a minimum underground depth from ground surface to top of the cable as per relevant standards: Provided that the underground power cable meant for use exceeding 33 kV shall be laid with a minimum underground depth of 1.2 metre. (2) No underground telecommunication cable shall be laid without a minimum separation distance of 0.3 metre 132 THE GAZETTE OF INDIA : EXTRAORDINARY [PART III—SEC.4] and 0.6 metre to the underground power cable of voltage up to 33 kV and exceeding 33 kV, respectively.

Previous and next

All provisions of Central Electricity Authority (Measures relating to Safety and Electric Supply) Regulations, 2023.

Questions people ask

Is regulation 79 of Central Electricity Authority (Measures relating to Safety and Electric Supply) Regulations, 2023. still in force?

No repeal of Central Electricity Authority (Measures relating to Safety and Electric Supply) Regulations, 2023. is recorded.