Safety and protective devices
76. Safety and protective devices. – (1) Every overhead line which is not being suspended from a dead bearer
wire, not being covered with insulating material and not being a trolley-wire, is laid over any part of a street or
other public place or in any factory or mine or on any consumer‟s premises shall be protected with earth
guarding for rendering the line electrically harmless in case its conductor breaks.
(2) An Electrical Inspector may, by notice in writing, require the owner of any such overhead line, wherever it
may be laid, to protect it in the manner specified in sub-regulation (1) of this regulation.
(3) To prevent bird dropping on the suspension insulator strings, suitable bird guards as per relevant standards,
shall be provided on cross arms of suspension tower or suspension pole structures, over the suspension insulator
strings.