Regulation 67, Central Electricity Authority (Measures relating to Safety and Electric Supply) Regulations, 2023.: General clearances
Central Electricity Authority (Measures relating to Safety and Electric Supply) Regulations, 2023. - Regulation 67
Text of regulation 67
General clearances
67. General clearances. – (1) For the purpose of computing the vertical clearance of an overhead line, the
maximum sag of any conductor shall be calculated on the basis of the maximum sag in still air and the maximum
temperature as specified under regulation 59 and computing any horizontal clearance of an overhead line the
maximum deflection of any conductor shall be calculated on the basis of the wind pressure specified under
regulation 59.
(2) No blasting for any purpose shall be done within three hundred metre from the boundary of a substation or
from the electric supply lines of voltage exceeding 650 V or tower structure thereof without the written
permission of the owner of such substation or electric supply lines or tower structures; and in case of mining
lease hold area, without the written permission of the Electrical Inspector of mines.
(3) No cutting of soil within ten metre from the tower structure of 110 kV and above voltage level shall be
permitted without the written permission of the owner of tower structure.
(4) No person shall construct brick kiln or other polluting units near the installations or transmission lines of 220
kV and above within a distance of 500 metre.