56. Supply to X-ray and high frequency installations. – (1) Any person, who proposes to use or who is using
electricity for the purpose of operating an X-ray or similar high-frequency installation, other than portable units
or shock-proof self contained and stationary units shall comply the following conditions, namely: –
(i) mechanical barriers shall be provided to prevent too close an approach to any parts of the X-ray
apparatus of voltage exceeding 650 V but not exceeding 33 kV, except the X-ray tube and its leads, unless
such parts of voltage exceeding 650 V but not exceeding 33 kV have been rendered shock proof by being
shielded by earthed metal or adequate insulating material;
(ii) where generators operating at 300 kV peak or more are used, such generators shall be installed in
rooms separate from those containing the other equipment and any step-up transformer employed shall be so
installed and protected as to prevent danger;
(iii) a suitable switch shall be provided to control the circuit supplying a generator and shall be so
arranged as to be open except while the door of the room housing the generator is locked from the outside;
(iv) X-ray tubes used in therapy shall be mounted in an earthed metal enclosure; and
(v) every X-ray machine shall be provided with a milliammeter or other suitable measuring instrument,
readily visible from the control position and connected, if practicable, in the earthed lead, but guarded if
connected in the lead of voltage exceeding 650 V but not exceeding 33 kV:
Provided that earth leakage circuit breaker of sufficient rating shall be provided on the side wherein
voltage does not exceed 250 V to detect the leakage in such X-ray installations.
[भाग III—खण्ड 4] भारतकाराजपत्र:असाधारण 123
Explanation. – For the purposes of this regulation “shock proof”, as applied to X-ray and high-frequency
equipment, shall mean that such equipment is guarded with earthed metal so that no person may come into
contact with any live part.
(2) In the case of nonshock proof equipment.-
(i) the overhead conductors of voltage exceeding 650 V but not exceeding 33 kV, unless suitably
guarded against personal contact, shall be adequately spaced and high voltage leads on tilting tables
and fluoroscopes shall be adequately insulated or so surrounded by barriers as to prevent inadvertent
contact;
(ii) the circuit of voltage not exceeding 250 V of the step up transformer shall contain a manually
operated control device having overload protection, in addition to the over current device for circuit
protection, and these devices shall have no exposed live parts and for diagnostic work there shall be an
additional switch in the said circuit, which shall be of one of the following types:-
(a) a switch with a spring or other mechanism that will open automatically except while held
close by the operator; or
(b) a time switch which will open automatically after a definite period of time for which it has
been set;
(iii) if more than one piece of apparatus be operated from the same source of voltage exceeding 650
V, each shall be provided with a switch of voltage exceeding 650 V to give independent control;
(iv) low frequency current-carrying parts of a machine of the quenched-gap or open gap type shall
be so insulated or guarded that they cannot be touched during operation but the high frequency circuit-
proper which delivers high-frequency current normally for the therapeutic purposes shall be exempt
from such insulation;
(v) all X-ray generators having capacitors shall have suitable means for discharging the capacitors
manually; and
(vi) except in the case of self-contained units, all 200 kV peak or higher X-ray generators shall have
a sphere gap installed in the system of voltage exceeding 650 V but not exceeding 33 kV adjusted so
that it will break down on over voltage surges.
(3) (i) all non-current carrying metal parts of tube stands, fluoroscopes and other apparatus shall be properly
earthed and insulating floors, mats or platforms shall be provided for operators in proximity to parts of
voltage exceeding 650 V unless such parts have been rendered shock proof; and
(ii) where short wave therapy machines are used, the treatment tables and examining chairs shall be
wholly non-metallic.
(4) The owner of any X-ray installation or similar high frequency apparatus shall not bring the same into use
without giving to the Electrical Inspector not less than fourteen days‟ notice in writing of his intention to do
so:
Provided that the aforesaid notice shall not be necessary in the case of shock-proof portable X-ray
and high-frequency equipment which have been inspected before the commencement of their use and
periodically thereafter.