43. Connection with earth. – The following conditions shall apply to the connection with earth of systems at
[भाग III—खण्ड 4] भारतकाराजपत्र:असाधारण 115
voltage exceeding 50 V but not exceeding 650 V, namely: –
(i) neutral conductor of a three phase, four-wire system and the middle conductor of a two-phase, three-wire
system shall be earthed as per the relevant standards;
(ii) neutral conductor shall also be earthed at one or more points along the distribution system or service line in
addition to any connection with earth which shall be at the consumer‟s premises;
(iii) in the case of a system comprising electric supply lines having concentric cables, the external conductor or
armour of such cables shall be earthed by two separate and distinct connections with earthing system;
(iv) in a direct current system, earthing and safety measures shall be as per the relevant standards;
(v) every building shall have protective equipotential bonding by interconnecting the exposed and extraneous
conductive parts as per the relevant standards;
(vi) the alternating current systems which are connected with the earth as provided in this regulation shall be
electrically interconnected:
Provided that each connection with the earth is bonded to the metal sheathing and metallic armouring, if
any, of the electric supply lines;
(vii) the frame of every generator, stationary motor, portable motor, and the metallic parts, not intended as
conductors, all transformers and any other apparatus used for regulating or controlling electricity, and all
electricity consuming apparatus, of voltage exceeding 250 V but not exceeding 650 V shall be earthed by two
separate and distinct connections with earth by the owner as specified in the relevant standards;
(viii) all metal casing or metallic coverings containing or protecting any electric supply line or apparatus shall be
connected with the earth and shall be so joined and connected across all junction boxes and other openings as to
provide good mechanical and electrical connection throughout the length:
Provided that the conditions mentioned in this regulation shall not apply, where the supply voltage does not
exceed 250 V and the apparatus consists of wall tubes or brackets, electroliers, switches, ceiling fans or other
fittings, other than portable hand lamps and portable and transportable apparatus, unless provided with the earth
terminal and to class-II apparatus and appliances of the relevant standards:
Provided further that where the supply voltage is not exceeding 250 V and where the installations are either
new or renovated, all plug sockets shall be of the three pin type, and the third pin shall be permanently and
effectively earthed;
(ix) All earthing systems shall, –
(a) consist of equipotential bonding conductors capable of carrying the prospective earth fault current
without exceeding the allowable temperature limits as per relevant standards in order to maintain all non-
current carrying metal works reasonably at earth potential and to avoid dangerous contact potentials being
developed on such metal works;
(b) have earth fault loop impedance sufficiently low to permit adequate fault current for the operation of
protective device within the time stipulated in the relevant standards; and
(c) be mechanically strong, withstand corrosion and retain electrical continuity during the life of the
installation and all earthing systems shall be tested to ensure effective earth bonding as per the relevant
standards, before the electric supply lines or apparatus are energised;
(x) all earthing systems belonging to the supplier shall in addition, be tested for resistance on dry day during
the dry season at least once in a year;
(xi) earth fault loop impedance shall be tested to ensure the automatic operation of the protective device and a
record of every earth test made and the result thereof shall be kept by the supplier for a period of not less than
two years after the day of testing and shall be available to the Electrical Inspector when required;
(xii) earth fault loop impedance of each circuit shall be limited to a value determined by the type and current
rating of the protective device used such that, on the occurrence of an earth fault, disconnection of the supply
shall occur before the prospective touch voltage reaches a harmful value; and
(xiii) the neutral point of every generator and transformer shall be earthed by connecting it to the earthing
system not by less than two separate and distinct connections.