Regulation 39, Central Electricity Authority (Measures relating to Safety and Electric Supply) Regulations, 2023.: Conditions applicable to installations of voltage exceeding 250 Volts
Central Electricity Authority (Measures relating to Safety and Electric Supply) Regulations, 2023. - Regulation 39
Text of regulation 39
Conditions applicable to installations of voltage exceeding 250 Volts
39. Conditions applicable to installations of voltage exceeding 250 Volts. – The following conditions shall be
complied with where electricity of voltage above 250 V is supplied, converted, transformed or used, namely: –
(i) all conductors, other than those of overhead lines, shall be completely enclosed in mechanically strong
metal casing or metallic covering which is electrically and mechanically continuous and adequately protected
against mechanical damage unless the said conductors are accessible only to a designated person or are installed
and protected so as to prevent danger:
Provided that non-metallic conduits conforming to the relevant standards may be used for installations of
voltage not exceeding 650 V;
(ii) all metal works, enclosing, supporting or associated with the installation, other than that designed to serve
as a conductor shall be connected with an earthing system as per relevant standards and the provisions of
regulation 43;
(iii) every switch board shall comply with the following, namely: –
(a) a clear space of not less than one metre in width shall be provided in front of the switchboard;
(b) if there are any attachments or bare connections at the back of the switchboard, the space, if any,
114 THE GAZETTE OF INDIA : EXTRAORDINARY [PART III—SEC.4]
behind the switchboard shall be either less than twenty centimetre or more than seventy five
centimetre in width, measured from the farthest protruding part of any attachment or conductor; and
(c) if the space behind the switchboard exceeds seventy five centimetre in width, there shall be a
passage way from either end of the switchboard, clear to a height of 1.8 metre;
(iv) in case of installations provided in premises where inflammable materials including gases and chemicals
are produced, handled or stored, the electrical installations, equipment and apparatus shall comply with the
requirements of flame proof, dust tight, totally enclosed or any other suitable type of electrical fittings depending
upon the hazardous zones as per the relevant standards;
(v) where an application has been made to a supplier for supply of electricity to any installation, the supplier
shall not commence the supply or where the supply has been discontinued for a period of six months or more,
recommence the supply unless the consumer has complied with the relevant provisions in these regulations;
(vi) where a supplier proposes to supply or use electricity at or to recommence supply of voltage exceeding 250
V but not exceeding 650 V after it has been discontinued for a period of six months, he shall, before connecting
or reconnecting the supply, give notice in writing of such intention to the Electrical Inspector; and
(vii) if at any time after connecting the supply, the supplier is satisfied that any provision of these regulations
have not been complied with, the supplier shall give notice of the same in writing to the consumer and the
Electrical Inspector, specifying the defects and to rectify such defects in a reasonable time:
Provided that if the consumer fails to rectify such defects the supplier may discontinue the supply
after giving the consumer a reasonable opportunity of being heard and recording reasons in writing and the
supply shall be discontinued only on written orders of an officer duly notified by the supplier in this behalf and
shall be restored with all possible speed after such defects are rectified by the consumer to the satisfaction of the
supplier.