Regulation 17, Central Electricity Authority (Measures relating to Safety and Electric Supply) Regulations, 2023.: Identification of earthed and earthed neutral conductors and position of switches and switchgear therein
Central Electricity Authority (Measures relating to Safety and Electric Supply) Regulations, 2023. - Regulation 17
Text of regulation 17
Identification of earthed and earthed neutral conductors and position of switches and switchgear therein
17. Identification of earthed and earthed neutral conductors and position of switches and switchgear therein. –
Where the conductors include an earthed conductor of a two-wire system or an earthed neutral conductor of a
multi-wire system or a conductor which is to be connected thereto, the following conditions shall be complied
with, -
(i) an indication of a permanent nature shall be provided by the owner of the earthed or earthed neutral
conductor, or the conductor which is to be connected thereto, to enable such conductor to be distinguished from
any live conductor and such indication shall be provided as per relevant standards, namely: –
(a) where the earthed or earthed neutral conductor is the property of the supplier, at or near the point of
commencement of supply;
(b) where a conductor forming part of a consumer‟s system is to be connected to the supplier‟s earthed
or earthed neutral conductor, at the point where such connection is to be made; and
(c) in all other cases, at a point corresponding to the point of commencement of supply.
(ii) no cut-out, link, switch or circuit breaker other than a linked switch arranged to operate simultaneously on
the earthed or earthed neutral conductor and live conductors shall be inserted or remain inserted in any earthed or
earthed neutral conductor of a two wire-system or in any earthed or earthed neutral conductor of a multi-wire
system or in any conductor connected thereto:
Provided that the above requirement shall not apply in case of a link for testing purposes, or a switch for
controlling a generator or transformer.