Form VI, The West Bengal Lift, Escalator And Travelator Rules, 2022: FORMVI
The West Bengal Lift, Escalator And Travelator Rules, 2022 - Form VI
Text of form VI
FORMVI
FORMVI
[See Rule 4(2) & Rule 21]
GENERALCHECKLISTFORLIFTINSTALLATIONS
(JOBNO.)
[PARrI
SI. Description Yes No Remarks
No.
1 Whether permanent supply upto the dedicated Main Switch MCCB for Lift is
available
2 Whether separate & dedicated single phase main switch'MCCB has been
provided for Lift shaft light
3 Whether Lift main switch provided at nearest convenient location in Lift loby
4 Whether the Lift Main Switches at Ground Floor have been earthed with 8
SWG G.I wire at two distinct points
5 Whether main switch earthings are done to the building earth bar
6 Whether building earth bar is connected with minimum two earth pits and those
are proper and marked as earth pits
7 Whether earth resistance at building earth bar measured & is within acceptable
limit
8 Whether proper marking on Lift main switch done
9 Whether civil jobs at each flow Lift landing positions completed
10 Whether each landing has a proper Lift lobby with Fire exit
11 Whether staircase hand rail guard at each floor provided
12 Whether staircase hand rail for machine room provided
13 Whether pit is cleaned and waterproof
14 Whether pit stop switches are available
15 Whether Pit light is working
16 Whether pit ladder is provided
17 Whether Shaft lights are working
18 Whether limit switches earthing done
19 Whether buffer foundations are properly done with R.C.C
20 Whether Lift lobby lights are provided at each floor
21 Whether counter-weight clamping or tie split pins provided
22 Whether counter guard net provided upto required height
23 Whether TOE-guard ofminimum 750 mm provided
24 Whether proper pit depth maintained as per IS 14665
25 Whether proper counter-weight run-by maintained as per IS 14665
26 Whether proper bottom clearance maintained as per IS 14665
27 Whether landing gate seal sap checked & found ok
PARrI] THEKOLKATAGAZETTE,EXTRAORDINARY, NOVEMBER 11, 2022 43
SI. Description Yes No Remarks
No.
28 Whether Facia for automatic door provided
29 Whether finishing done below the landing door seal for manual door
30 Whether car lights are kept direct
31 Whether alarm bell checked and found ok
32 Whether all LEDs of floor indicator etc are working
33 Whether all lights, fan inside car are working
34 Whether gate locks at each flow checked & found ok
35 Whether proper top clearance maintained as per IS 14665
36 Whether machine room door is outside opening and made ofFire Proof
weather proof as per IS 14665
37 Whether metal 415 V danger plate outside machine room door provided
38 Cheeked for any water ingress source to machine room through window,
exhaust etc
39 Machine room main switch properly earthed at two distinct points with 8 swg G.I
40 Whether proper light & ventilation in machine room provided
41 All earthing wires, controller wiring etc are properly dressed
42 Lift machine properly installed &fastner bolt provided
43 Whether rope end are property seated
44 All limit switched (up-down final, governor safety) installed at requisite location
45 Whether Governor name plate with tripping speed fixed on governor body
46 Whether extra cut-out on machine room floor has been properly covered
47 Whether UP & Down final limit checked & found ok
48 Governor safety (both electrical & mechanical) checked and found ok
49 Whether load balancing checked & found in order
50 Load test (if done on the hook at machine room) has been tagged
51 Whether governor switch and car safety switch or both the switches
aremanually operable
52 Whether Governor actuation facility from control panel provided for MRL Lift
53 WhetherManual Rescue Device provided forMRL Lift
54 Whether controller maintenance access panel besides top floor landing
forMRLLift
55 Whether separate brake contactor provided in case ofMetal metal contact
56 Whether clear laminated safety glass used & certificate available in case ofglass
Lift/shaft
57 Whether dynamic brake incorporated in case of drive
58 Whether cover for the dynamic resistance provided in case of installation
outsidepanel
59. Whether Stop Switch provided in Car and found working
44 THE KOLKATAGAZETTE,EXTRAORDINARY, NOVEMBER 11, 2022 [PARrI
Previous and next
All provisions of The West Bengal Lift, Escalator And Travelator Rules, 2022
Questions people ask
Is form VI of the West Bengal Lift, Escalator And Travelator Rules, 2022 still in force?
No repeal of the West Bengal Lift, Escalator And Travelator Rules, 2022 is recorded.