Rule 59, Tamil Nadu Combined Development and Building Rules, 2019: Boiler Room
Tamil Nadu Combined Development and Building Rules, 2019 - Rule 59
Text of rule 59
Boiler Room
59. Boiler Room.— The following aspects may be taken into account in the location of
Boiler or Boiler Room:
(a) The boiler shall not be allowed in sub-basement but be allowed in the first
basement away from the escape routes.
(b) The boilers shall be installed in a fire resisting room of 4 hours fire resistance
rating, and this room shall be situated on the periphery of the basement. Catch pit
shall be provided at the low level. Entry to this room may be provided with a
composite door of two hour fire resistance.
(c) The boiler room shall be provided with fresh air inlets and smoke exhausts directly
to the atmosphere.
(d) Foam inlets shall be provided on the external walls of the building at the ground
floor level to enable the fire services to use foam in case of fire.
(e) The furnace oil tank for the boiler, if located in the adjoining room shall be
separated by fire resisting wall of 4 hour rating. Entry to this room shall be
provided with a composite door of 2 hour fire resistance. A curb of suitable height
shall be provided at the entrance in order to prevent the flow of oil into the boiler
room in case of tank rupture.