Rule 46, Tamil Nadu Combined Development and Building Rules, 2019: Electrical Transformer Rooms
Tamil Nadu Combined Development and Building Rules, 2019 - Rule 46
Text of rule 46
Electrical Transformer Rooms
46. Electrical Transformer Rooms.— Electrical rooms in Non High Rise Buildings and
High Rise Building developments shall conform to the following:
(1) Tamil Nadu Electricity Board- Tamil Nadu Generation and Distribution Corporation
(TANGEDCO) Standards:-
(a) Indoor space required within the premises for installing floor mounted
distribution transformer and associated switchgear.
(i) An electrical room for accommodating the transformers and associated
switchgears shall be provided at the ground floor, either within the built
up space of the buildings or outside the buildings and within the premises
of the buildings nearer the main entrance of the building. The associated
switchgear shall be separated from the transformer bays by a fire-resisting
wall with a fire resistance of not less than 4 (four) hours.
(ii) The width of the approach road to the above said electrical room shall not
be less than 3.0 metres.
(iii) The electrical room with RCC roof shall have clear floor area 6m. X 4m.
with a vertical clearance of 2.75m.
(iv) Three sides of this room shall be covered with brick walls. The fourth
side, towards the approach road shall be covered with M.S. Rolling Grill
Shutter of width not less than 3 metres with locking facility.
(v) The electrical room shall be fitted with 2 Nos. exhaust fans in the wall
facing the approach road, one on either side of the shutter.
(vi) The electrical room shall have raised cement flooring with cable duct of
450-mm. width and 750-mm. depth, all around inside the room and close
to the exterior walls shutters. The flooring shall slope towards the cable
duct. The cabled duct shall be covered with RCC slabs of thickness not
less than 75 mm. (3 inches). The covered slabs shall flush with the
cement flooring. The radius of curvature of the cable ducts at the
turnings inside the electrical room shall not be less than one metre.
(b) The open space within the premises for installation.
A clear space of 10m. x 4m. or 5m. x 5m. open to the sky and having an
approach road of width not less than 3 metres, upto the public road shall be
provided within the consumer premises, preferably at the main entrance.
(2) Directorate of Fire and Rescue Services Standards:
(i) No transformer shall be located below the first basement or above the
ground floor
(ii) A sub-station or switch station with apparatus having more than 2000 litres oil
shall not be allowed in the case of indoor transformer.
(iii) The indoor transformer should preferably be housed in a fireproof room with
walls and doors sufficient fire rating.
(iv) The room in the ground floor of the basement housing the transformer shall
have a free access to the outside.
(v) There shall be a curb or a dwarf wall around the transformer so that oil spills if
any, is contained within the curb. There shall also be a suitable drain with a '
flame-arrester'
TAMIL NADU GOVERNMENT GAZETTE EXTRAORDINARY 57
(vi) If in the basement, the transformers shall be adequately protected against fire
by a high velocity water spray or a CO2 flooder of suitable capacity, depending
upon the size of the transformer.
(vii) The switchgears, if any shall be housed in a separate room with suitable fire
resistance walls.
(viii) The transformers shall be located only in the periphery of the basement or
ground floor, observing suitable clearances.
(ix) DCP or CO2 portable fire extinguishers of a minimum capacity of 10 kg. shall
be kept near the doorway housing the transformer.
(x) All indoor transformers shall be subjected to periodic inspection and shall be
replaced in good time so that there is no fire risk.
(xi) The room shall be well ventilated so that the transformer remains cool.
(xii) The room shall have emergency and automatic lighting with independent power
supply.