Rule 75, The Karnataka Cinemas (Regulation) Rules, 2014.: Fire Fighting apparatus
The Karnataka Cinemas (Regulation) Rules, 2014. - Rule 75
Text of rule 75
Fire Fighting apparatus
75. Fire Fighting apparatus.- (1) The following fire fighting appliances shall be
provided in every cinema or multiplex building, namely:-
(a) In projection room-
(i) One water gel blanket
(ii) Two buckets of water, each of 09 liters capacity.
(iii) Two carbon dioxide extinguishers, each of two kg capacity and one
carbon dioxide extinguisher of 5 kg capacity.
(b) In auditorium and balcony.-
(i) Four ABC powder extinguishers, each of 5 kg capacity in the auditorium
and two such extinguishers in the balcony wherever balcony is in
existence.
(ii) Two stirrup pumps attached with flexible hoses of not less than six
meters in length in the auditorium and one stirrup pump in the balcony
wherever balcony is in existence. Each stirrup pump shall be provided
with two flat bottom buckets each of ten liters capacity to be kept always
filled with water; and inbuilt firefighting equipment as required shall be
provided.
(iii) Two carbon dioxide extinguishers, each of two kg capacity and one
carbon dioxide extinguisher of 5 kg capacity.
(iv) One fire bucket of ten liters capacity filled with water for every one
hundred square meters of floor area or part thereof with a minimum of
twelve buckets in the auditorium and two in the balcony.
(c) Near electrical installation,-
(i) One ABC powder extinguishers of 5 kg capacity near each main switch
board.
(ii) Wherever electrical meters, rotary convertors or any other electrical
machinery or apparatus are installed, one ABC powder extinguisher of 5
kg capacity shall be provided.
(2) All fire fighting appliances shall be kept in such a manner as to be readily available
for use. The majority of the fire fighting appliances in the auditorium shall be fitted in the
neighborhood of the screen at a height of 1.20 m.
(3) The fire buckets shall have round bottoms, each of 9 liters capacity. They shall be
painted red with the word “Fire” in large white letters in English, Hindi and Kannada filled with
clean, dry sand.
(4) All the portable extinguishers shall be maintained periodically and subjected to
hydraulic pressure test at the jurisdictional Fire Station or an engineering firm authorized in
this behalf by the Government, to show that it can withstand for one minute a pressure of
twenty kg/cm2 and a certificate of such test shall be submitted to the Licensing Authority.
Similar tests shall be repeated annually thereafter.
(5) The attendants, staff including the cinema operator of
Previous and next
All provisions of The Karnataka Cinemas (Regulation) Rules, 2014.
Questions people ask
Is rule 75 of the Karnataka Cinemas (Regulation) Rules, 2014. still in force?
No repeal of the Karnataka Cinemas (Regulation) Rules, 2014. is recorded.