Rule 58, The Karnataka Cinemas (Regulation) Rules, 2014.: Main Circuits
The Karnataka Cinemas (Regulation) Rules, 2014. - Rule 58
Text of rule 58
Main Circuits
58. Main Circuits.- (1) The electric lighting of the premises shall have at least three
separate and distinct main circuits and these shall be,-
(i) Circuit ‘A’ for the projection room and then, through dimming regulator if any, to the
central lighting of the auditorium,
(ii) Circuit ‘B’ for approximately one half of the auditorium, passage ways, stair ways,
exits and parts of the buildings open to the public and
(iii) Circuit ‘C’ for the remaining half of the auditorium, passage ways, stair ways, exits
and parts of the buildings open to the public
(2) The control of the circuits in respect of ‘B’ and ‘C’ shall be remote from each other.