Rule 144, The West Bengal Municipal (Building) Rules, 2007: Staircase
The West Bengal Municipal (Building) Rules, 2007 - Rule 144
Text of rule 144
Staircase
144. Staircase.—
(1) In every domestic building, more than one storey in height, the principal staircase shall have a width of not less
than 1 metre in every flight:
Provided that where the building is constructed or adopted to be occupied in flats or tenements, the width of the
principal staircase serving more than two suites per floor shall be increased by 8 centimetres in every flight for every
additional suites on a floor.
(2) Every such staircase shall be adequately lighted and ventilated by windows of not less than 1 sq. metre in area
per storey.
(3) No wooden staircase will be allowed.
(4) Minimum clear head room in any staircase shall be two metres and twenty five centimetres as measured from
the top of the riser to the lowest position of the ceiling or beam perpendicularly above it.
(5) Every staircase shall be provided with treads of not less than twenty-five centimetres in width and not more than
eighteen centimetres in rise without winders with landings of width not less than that of the staircase. The treads and rise
of each flight of stairs in such staircase shall be of uniform width and height. (The staircase landing from first floor and
above may project from the building line in the wider side space up to a maximum width of 1 metre only.) Clear height of
such projected landing above ground level shall be 2.25 m minimum. Similar projection of 1 metre of staircase landing
from the building line may also be allowed in the back space for corner plots where no wider side space exists or where
the wider side space is reduced to counterbalance the difficulty in planning, but a clear gap of 1.5 metre must always be
kept from the property line. Further projection beyond this line will, however not be allowed in the shape of chajja or in
any other form. This projection will, however, not be allowed in back spaces for rectangular plot, nor in the front spaces
or in the narrower side spaces of any plot. In the case of buildings other than residential or hazardous building, a staircase
shall be provided for every 300 persons who are expected to use the building. No staircase shall be less than 1.5 metre (5
ft) in width and the farthest corner of the building shall not be more than 18 m (60 ft) distant from the staircase. The width
of landing at the roof level for all categories of plots shall not be wider than the minimum width of stair flight:
Provided that lift (as per provisions of rule 63) shall have to be provided for a building beyond 13.5 m height from
the Ground Level but the lift machine room will be as per latest edition of the National Building Code. The lift machine
room will not be included while calculating floor area.
Note.—Lift may also be provided in any building other than mentioned above as per norms stated in these rules.