Rule 43, The West Bengal Municipal (Building) Rules, 2007: Distance from electric lines

The West Bengal Municipal (Building) Rules, 2007 - Rule 43

Text of rule 43

Distance from electric lines

43. Distance from electric lines.— No building, or verandah, or balcony or projection in any building shall be permitted to be erected, re-erected, added to or altered, in any case where the distance between such construction and any overhead electric lines, in accordance with the provision of the Electricity Act, 2003 (36 of 2003), is less than that specified hereinafter:— Vertical clearance Horizontal clearance (a) Low and medium voltage lines including service lines 2.5 m 1.2 m (b) High voltage lines up to and including 11,000 volts 3.7 m 1.2 m (c) High voltage lines above 11,000 volts and up to and 3.7 m 2.0 including 33,000 volts (d) For extra high voltage lines 3.7 m plus 0.3 m for every 2.0 m plus 0.3 m for beyond 33,000 volts additional 33,000 volts or everyadditional 33,000 parts thereof volts or parts thereof Note : "m" indicates Metre. 24 THE KOLKATA GAZETTE, EXTRAORDINARY, FEBRUARY 14, 2007 [PART I