Rule 43, The West Bengal Municipal (Building) Rules, 2007: Distance from electric lines
The West Bengal Municipal (Building) Rules, 2007 - Rule 43
Text of rule 43
Distance from electric lines
43. Distance from electric lines.—
No building, or verandah, or balcony or projection in any building shall be permitted to be erected, re-erected, added
to or altered, in any case where the distance between such construction and any overhead electric lines, in accordance
with the provision of the Electricity Act, 2003 (36 of 2003), is less than that specified hereinafter:—
Vertical clearance Horizontal clearance
(a) Low and medium voltage
lines including service lines 2.5 m 1.2 m
(b) High voltage lines up to and
including 11,000 volts 3.7 m 1.2 m
(c) High voltage lines above
11,000 volts and up to and 3.7 m 2.0
including 33,000 volts
(d) For extra high voltage lines 3.7 m plus 0.3 m for every 2.0 m plus 0.3 m for
beyond 33,000 volts additional 33,000 volts or everyadditional 33,000
parts thereof volts or parts thereof
Note : "m" indicates Metre.