Rule 56, THE CHHATTISGARH CINEMAS (REGULATION) RULES, 1972: Cut-outs
THE CHHATTISGARH CINEMAS (REGULATION) RULES, 1972 - Rule 56
Text of rule 56
Cut-outs
56. Cut-outs.—(1) All circuits shall be sufficiently protected by cut -outs
placed in posit ions easily accessible to t he staff , but inaccessible to the public. All
cut -outs shall be of such pattern and be fixed in such a posit ion as to admit of quick
replacement.
25
(2) All cut-outs shall be so constructed that fall ing fused metal cannot cause a
short circuit or an igni t ion.
(3) All switches and cut -outs shall be so marked as to show clearly which
circuit or lamp they control .
(4) All switches and cut -outs ceil ing roses and wall sockets lamps -holders shall
have no-inflammable bases and covers. All switches and cut -outs shall have sufficient
length and breadth and shall be constructed so as to prevent the risk of formation of
an arc.
(5) All switches shall be of ample size to carry the current for which they are
intended without heating and shall be so constructed that they sha l l not remain in any
posit ion intermediate between the on and the "off" posit ion so as to permit of an arc
or short circuit .