Rule 43, THE CHHATTISGARH CINEMAS (REGULATION) RULES, 1972: Conductors f ixing and protection
THE CHHATTISGARH CINEMAS (REGULATION) RULES, 1972 - Rule 43
Text of rule 43
Conductors f ixing and protection
43. Conductors f ixing and protection.— (1) All conductors including lead
covered cables where accessible to the public shall be efficiency protected from
mechanical injury by an external armour of iron or steel .
(2) Where conductors pass through or within walls f ire -proof floors or ceil ing,
they shall be protected by iron pipes or by glazed stoneware or porcelain tubes and
22
precautions shall be taken to prevent the possibil i ty of f ire water passing along the
course of the conductors.
(3) Conductors shall not be placed where l iable to be heated by jets, steam
pipes or other appliances.
(4) In special cases, or where necessary for protection from the depredations of
rats, mice or other vermin, the wiring shall be enclosed in heavy gauge steel conduit .