Rule 33, The Maharashtra Factories Rules, 1963: How to introduce steam for humidification
The Maharashtra Factories Rules, 1963 - Rule 33
Text of rule 33
How to introduce steam for humidification
33. How to introduce steam for humidification.- In any room in which steam
pipes are used for the introduction of steam for the purposes of artificial
humidification of the air the following provision shall apply:-
(a) The diameter of such pipes shall not exceed 5 mm. and in the case of pipes
installed after 1st day of January 1950 the diameter shall not exceed 25
mm.
(b) Such pipes shall be as short as is reasonably practicable.
(c) All hangers supporting such pipes shall be separated from the bare pipes
by an efficient insulator not less than 15 mm. in thickness.
(d) No uncovered jet from such pipes shall project more than 100 mm. beyond
the outer surface of any cover.
(e) The steam pressure shall be as low as practicable and shall not exceed 5
kgs. per square centimetre.
(f) The pipes employed for the introduction of steam into the air in a
department shall be effectively covered, with such non-conducting material
as may be approved by the Inspector.