Rule 72, The Factory rules 1962: Fire Protection
The Factory rules 1962 - Rule 72
Text of rule 72
Fire Protection
[72. Fire Protection. - (1) Processes, equipment, plant, etc. involving serious
explosion and serious fire hazards. -
(a) All processes, storages, equipments, plant, etc., involving serious explosion and
flash fire hazards shall be located in segregated buildings where the equipment shall
be so arranged that only minimum number of employees are exposed to such
hazards at any one time.
(b) All industrial processes involving serious fire hazard shall be located in buildings or
work places separated from one another by walls of fire-resistant construction.
(c) Equipment and plant involving serious fire or flash fire hazards shall, whenever
possible be so constructed and installed that in case fire, they can be easily isolated.
(d) Ventilation ducts, pneumatic conveyors and similar equipment involving a serious
fire is risk shall be provided with flamerresting or automatic fire extinguishing
appliances, or fire resisting dampers electrically interlocked with heat sensitive/smoke
detectors and the air-conditioning plant system.
(e) In all work places having serious fire or flash fire hazards, passages between
machines, installations or piles of material shall be at least 90 cm. wide. For storage
piles, the clearance between the ceiling and the top of the pile shall not be less than 2
m.
(2) Access for the fighting. -
(a) Buildings and plants shall be so laid out and roads, passageways etc., so
maintained as to permit unobstructed access for fire fighting.
(b) Doors and window openings shall be located in suitable positions on all external
walls of the building to provide easy access to the entire area within the building for
fire fighting.
(3) Protection against lightening. - Protection from lightening shall be provide for-
(a) buildings in which explosive or highly flammable substances are manufactured,
used, handled or stored;
(b) storage tanks containing oils, paints or other flammable liquids;
(c) grain elevators;
(d) buildings, tall chimneys or stacks where flammable gases, fumes, dust or lint are
likely to be present; and
(e) substation buildings and out-door transformers and switch yards.
(4) Precautions against ignition. - Wherever there is danger of fire or explosion for
accumulation of flammable or explosive substances in air-
(a) all electrical apparatus shall either be excluded from the area of risk or they shall
be such construction and so installed and maintained as to prevent the danger of their
being a source of ignition;
(b) effective measures shall be adopted for prevention of accumulation of static
charges to a dangerous extent;
(c) workers shall wear shoes without iron or steel nails or any other exposed ferrous
materials which is likely to cause sparks by friction,
(d) smoking, lighting or carrying of matches, lighters or smoking materials shall be
prohibited;
(e) transmission belts with iron fastness shall not be used; and
(f) all other precautions, as are reasonably practicable, shall be taken to prevent
initiation of ignition from all other possible sources such as open flammes, frictional
spark overheated surfaces of machinery or plants, chemical or physical-chemical
reaction and radiant heat.
(5) Spontaneous ignition. - Where materials are likely to induce spontaneous
ignition, care shall be taken to avoid formation of air pocket and to ensure adequate
ventilation. The material susceptible to spontaneous ignition should stored in dry
condition and should be in heaps of such capacity and separated by such passage
which will prevent fire. The materials susceptible to ignition and stored in the open
shall be at a distance not less than 10 metres away from process or storage buildings.
(6) Cylinders containing compressed gas. - Cylinders containing compressed gas
may only be stored in open if they are protected against excessive variation of
temperature, direct rays of sun, or continuous dampness. Such cylinder shall never be
stored near highly flammable substances, furnaces or hot processes. The room
where such cylinders are stored shall have adequate ventilation.
(7) Storage of flammable liquids. - (a) The quantity of flammable liquids in any work
room shall be the minimum required for the process or processes carried on in such
room. Flammable liquids shall be stored in suitable containers with closed fitting
covers :
Provided that not more than 20 litres of flammable liquids having a flash point of 21 "C
or less shall be kept or stored in any work room.
(b) Flammable liquids shall be stored in closed containers and in limited quantities in
well ventilated rooms of fire resisting construction which are isolated from the
remainder of the building by fire walls and self closing fire doors.
(c) Large quantities of such liquids shall stored in isolated adequately ventilated
building of fire resisting construction or in storage tanks, preferably underground and
at a distance from any building as required in the Petroleum Rules, 1976.
(d) Effective steps shall be taken to prevent leakage of such liquids into basements,
slumps or drains and to confine any escaping within safe limit.
(8) Accumulation of flammable dust, gas, fume or vapour in air or flammable
waste material on-the floors. - (a) Effective steps shall be taken for removal or
prevention of the accumulation in the air of flammable dust, gas, fume or vapour to an
extent which is likely to be dangerous.
(b) No waste material of a flammable nature shall-be permitted to accumulate on the
floors and shall be removed at least once in a day or shift, and more often, when
possible. Such materials shall be placed in suitable metal containers with covers
wherever possible.
(9) Fire exits. - (a) In this Rule :-
(i) "horizontal exit" means an arrangement which allows, alternative egress from a
floor area to another floor at or near the same level in an adjoining building or an
adjoining part of the same building with adequate separation; and
(ii) "travel distance" means the distance an occupant has to travel to reach at exit.
(b) An exit may be doorway, corridor, passageway, to an external stairway or to a
verandah or to an internal stairway segregated from the rest of building by fire
resisting walls which shall provide continuous and protected means of egress to the
exterior of a building or to an exterior open space. An exit may also include a
horizontal exit leading to an adjoining building at the same level.
(c) Lifts, escalators and revolving doors shall not be considered as exits for the
purpose of this sub-rule.
(d) In every room of a factory exits sufficient to permit safe escape of the occupants in
case of fire or other emergency shall be provided which shall be free of any
obstruction.
(e) The exit shall be clearly visible and suitably illuminated with suitable arrangement,
whatever artificial lighting is to be adopted for this purpose, to maintain the required
illumination in case of failure of the normal source of electric supply.
(f) The exits shall be marked in a language understood by the majority of the workers.
(g) Iron rung ladders or spiral staircases shall not be used as exit staircases.
(h) Fire resisting doors or roller shutters shall be provided at appropriate places along
with the escape routes to prevent spread of fire and smoke, particularly at the
entrance of lifts or stairs where tunnel of the flue effect may be created inducing an
upward spread of fire.
(i) All exits shall provide continuous means of egress to the exterior of a building or to
an exterior open space leading to a street.
(j) Exits shall be so located that the travel distance to reach at least one of them on the
floor shall not exceed 30 metres.
(k) In case of those factories where high hazard materials are stored or used, the
travel distance to the exit shall not exceed 22.5 metres and there shall be at least two
ways of escape from every room, however small, except toilet rooms, so located that
the points of access thereto are out of or suitably shielded from areas of high hazard.
(l) Wherever more than one exit is required for any room space or floor, exits shall be
placed as remote from each other as possible and shall be arranged to provide direct
access in separate directions from any point in the area served.
(m) The unit of exit width used to measure capacity of any exit shall be 50 cm. A clear
width of 25 cm. shall be counted as an additional half unit. Clear width of less than 25
cm. shall not be counted for exit width.
(n) Occupants per unit width shall be 50 for stairs and 75 for doors.
(o) For determining the exits required, the occupant load shall be reckoned on the
basis of actual number of occupants within any floor area of 10 square meters per
person whichever is more.
(p) There shall not be less than two exits serving every floor area above and below the
ground floor, and at least one of them shall be an internal enclosed stairway.
(q) For every building or structure used for storage only, and every section thereof
considered separately, shall have access to atleast one exit so arranged and located
as to provide a suitable means of escape for any person employed therein, and in any
such room wherein more than 10 persons maybe normally present, at least two
separate means of exit shall be available, as remote from each other as practicable.
(r) Every storage area shall have access to at least one means of exit which can be
readily opened.
(s) Every exit doorway shall open into an enclosed stairway, a horizontal exit on a
corridor or passageway providing continuous and protected means of egress.
(t) No exit doorway shall be less than 100 cm. in width, doorways shall be not less
than 200 cm. in height.
(u) Exit doorways shall open outwards, that is, away from the room but shall not
obstruct the travel along any exit. No door when opened, shall reduce the required
width of stairway of landing to less than 90 cm. Over head or sliding doors shall not be
installed for this purpose.
(v) An exit door shall not open immediately upon a flight or stairs. A landing atleast 1.5
m. X 1.5 m. in size shall be provided in the stairway at each doorway. The level of
landing shall be the same as that of the floor which it serves.
(w) The exit doorways shall be openable from the side which they serve without the
use of a key.
(x) Exit corridors and passageways shall be of a width not less than the aggregate
required width of exit doorways leading from there in the direction of travel to the
exterior.
(y) Where stairways discharge through corridors and passageways, the height of the
corridors and passageways shall not be less than 2.4 meters.
(aa) A staircase shall not be arranged round a lift shaft unless the later is totally
enclosed by a material having a fire-resistance rating not lower than that of the type of
construction of the former.
(bb) Hollow combustible construction shall not be permitted
(cc) The minimum width to treads without nosing shall be 25 cm. for an internal
staircase. The treads shall be constructed and maintained in a manner to prevent
slopping.
(dd) The maximum height of a riser shall be 19 cm. and the number of risers shall be
limited to 12 per flight.
(ee) Hand rails shall be provided with a minimum height of 100 cm. and shall be firmly
supported.
(ff) The use of spiral staircase shall be limited to low occupant load and to a building of
height of 9 metres, unless they are connected to platforms such as balconies and
terraces to allow escapes to pause. A spiral staircase shall be not less than 300 cm. in
diameter and have adequate head room.
(gg) The width of a horizontal exit shall be same as for the exit doorways.
(hh) The horizontal exit shall be equipped with atleast one fire door of self closing
type.
(ii) The floor area on the opposite or refuge side of a horizontal exit shall be sufficient
to accommodate occupants of the floor areas served, allowing not less than 0.3
square meter per person. The refuge area shall be provided with exits adequate to
meet the requirements of this sub-rule. Atleast one of the exits shall lead directly to
the exterior or street.
(jj) Where there is difference in level between connected areas for horizontal exit,
ramps not more than 1 into 8 slope shall be provided. For this purpose steps shall not
be used.
(kk) Doors in horizontal exits shall be openable at all times.
(ll) Ramps with a slope of not more than 1 into 10 may be substituted for the
requirements of staircase. For all slopes exceeding I to 10 and wherever the use is
such as to involve danger of slipping, the ramp shall be surface with non-slipping
material.
(mm) In any building not provided with automatic fire alarm a manual fire alarm
system shall be provided if the total capacity of the building is over 500 persons, or if
more than 25 persons are employed above or below the ground floor, except that no
manual fire alarm shall be required in one-storey buildings where the entire area is
undivided and all parts thereof are clearly visible to all occupants.
(10) First-aid fire fighting arrangements. - (a) In every factory there shall be
provided and maintained adequate and suitable fire fighting equipment for fighting
fires in the early stages, those be in referred to as first-aid fire fighting equipment in
this rule.
(b) The types of first-aid fire fighting equipment to be provided shall be determined by
considering the different types of fire risks which are classified as follows :
(i) "Class A fire". - Fire due to combustible materials such as wood, textiles, paper,
rubbish and the like-
1. "Light hazard"-Occupancies like offices, assembly halls, canteens,
restrooms, ambulance rooms and the like;
2. "Ordinary hazard"-Occupancies like saw mill carpentry shop, small timber
yards book-binding shops, engineering workshop and the like;
3. "Extra hazard"-Occupancies like large timber yards, godowns storing
fibrous materials, flour mills, cotton mills, jute mills, large wood working
factories and the like;
(ii) "Class B fire". - Fire inflammable liquids like oil, petroleum products, solvent,
grease, paint, etc.
(iii) "Class C fire". - Fire arising out of gaseous substances.
(iv) "Class D fire". - Fire from reactive chemicals, active metal and the like.
(v) "Class E fire". - Fire involving electrical equipment and delicate machinery and
the like.
(c) The number and types of first-aid fire fighting equipment to be provided for 'light
hazard' occupancy shall be as given in Schedule to the rule. For "ordinary hazard or
extra hazard" occupancies equipment as given in paragraph 12 shall be provided in
addition to that given in Schedule I.
(d) The first-aid fire fighting equipment shall confirm to the relevant Indian Standards.
(e) As far as possible the first-aid fire fighting equipment shall all be similar in shape
and appearance and shall have the same method of operation.
(f) All first-aid fire fighting equipment shall be placed in a conspicuous position and
shall be readily and easily accessible for immediate use. Generally, these equipments
shall be placed as near as possible to the exits or stair landing or normal routes of
escape.
(g) All water buckets and bucket pump type extinguishers shall be filled with clean
water. All sand buckets shall be filled with clean, dry and fine sand.
(h) All other extinguishers shall be charged appropriately in accordance with the
instructions of the manufacturer.
(i) Each first-aid fire fighting equipment shall be allotted a serial number by which it
shall be referred to in the records. The following details shall be painted with white
paint on the body of each equipment :-
1. Serial number;
2. Date of last refilling; and
3. Date of last inspection.
(j) First-aid fire fighting equipment shall be placed on platforms or in cabinets in such a
way that their bottom is 750 mm. above the floor level. Fire bucket shall be placed on
books attached to a suitable stand or wall in such a way that their bottom is 750 mm.
above the floor level. Such equipment if placed outside the building, shall be under
sheds or covers.
(k) All extinguishers shall be thoroughly cleaned and re-charged immediately after
discharge. Sufficient refill material shall be kept readily available for this purpose at all
times.
(l) All first-aid fire fighting equipment shall be subjected to routine maintenance,
inspection and testing to be carried out by properly trained persons. Periodically of the
routine maintenance, inspection and test shall confirm to the relevant Indian
Standards.
(11) Other fire fighting arrangements. - (a) In every factory, adequate provision of
water supply for fire righting shall be made and where the amount of water required in
liters per minute as calculated from the formula A+B+C+D divided by 20 is 550 or
more, power driven trailor pumps of adequate capacity to meet the requirement of
water as calculated above shall be provided and maintained.
In the above formula-
(A) the total area is square meters of all floors including galleries in all buildings of the
factory;
(B) the total area in square metres of all floors and galleries including open spaces in
which combustible materials are handled or stored;
(C) the total area in square metres of all floors over 15 metres above ground level;
and
(D) the total area in square metres of all floors of all buildings other than those of fire
resisting construction :
Provided that in areas where the fire risk involved does not require use of water, such
areas under B, C or D may, for the purpose of calculation, be halved :
Provided further that where the areas under B, C or D are protected by permanent
automatic fire fighting installations approved by any fire association or fire insurance
company such areas may, for the purpose of calculation, be halved :
Provided also that where the factory is situated not more than 3 kilometres from an
established city or town fire service the pumping capacity based on the amount of
water arrived at by the formula above may be reduced by 25%, but no account shall
be taken of this reduction in calculating water supply required under clause (a).
(b) Each trailer pump shall be provided with equipment as per Schedule II appended
to this rule. Such equipment shall confirm to the relevant Indian Standards.
(c) Trailer pumps shall be housed in a separate shed or sheds which shall be sited
closed to a principal source of water supplied in the vicinity of the main risks of the
factory.
(d) In factories where the area is such as cannot be reached by man-hauling of trailer
pumps within reasonable time vehicles with towing attachment shall be provided at
the scale of one for every four trailer pumps with a minimum of one such vehicle kept
available at all times.
(e) Water supply shall be provided to give flow of water as required under clause (a)
for atleast 100 minutes. Atleast 50% of this water supply or 4,50,000 litres whichever
is less, shall be in the form of static tanks of adequate capacities (not less than
4,50,000 litres each) distributed round the factory with the regard to the potential fire
risks in the factory. Where piped supply is provided, the size of the main shall be
capable of supplying a minimum of 4500 litres per minute at a pressure of not less
than 7 kilogram per square centimetre.
(f) All trailer pumps including the equipment provided with them and the vehicles for
towing them shall be maintained in good condition and subject to periodical inspection
and testing as required.
(12) Personnel in charge of equipment and for fire fighting, fire drills, etc.
- (a) The first-aid and other fire fighting equipment to be provided as required in
sub-rules (1) and (11) shall be incharge of a trained responsible person.
(b) Sufficient number of persons shall be trained in the proper handling of fire fighting
equipment as referred to in clause (a) and their use against the types of fire for which
they are intended to ensure that adequate number of persons are available for fire
fighting both by means of first-aid fire fighting, equipment and others. Such persons
shall be provided with clothing and equipment including helmets, belts and boots,
preferably gumboots. Wherever vehicles with towing attachment are to be provided as
required in clause (d) of sub-rule (11) sufficient number of persons shall be trained in
driving these vehicles to ensure that trained persons are available for driving them
wherever the need arises.
(c) Fire fighting rills shall be held as often as necessary and at least once in every
period of 2 months.
(13) Automatic sprinklers and fire hydrants shall be in addition and not in substitution
of the requirements in sub-rules (10) and (11).
(14) If the Chief Inspector is satisfied in respect of any part of the factory that owing to
the exceptional circumstances such as inadequacy of water supply or infrequency of
the manufacturing process or for any other reason, to be recorded in writing, all or any
of the requirements of the rules are impracticable or not necessary for the protection
of workers, he may by order in writing (which he may at his discretion revoke) exempt
such factory or part of the factory from all or any of the provisions of the rules subject
to conditions as he may by such order prescribe.
Schedule I
First Aid Fire Fighting Equipments
(1) The different type of fires and first aid fire fighting equipments suitable for use on
them an- as under :-
Class of fire Suitable type of
appliances
A.
Fires in ordinary
combustibles (wood,
vegetable fibres, paper
and the like).
Chemical Extinguishers of
Soda-acid, Gas/expelled
water and antifreeze types,
and water buckets.
B.
Fires inflammable
liquids, paints, grease
solvents and the like.
Chemical Extinguishers of
foam, Carbon dioxide and
dry powder types and sand
buckets.
C.
Fires in gaseous
substances under
pressure.
Chemical Extinguishers of
carbon dioxide and dry
powder types.
D.
Fires in Reactive
Chemicals, active metal
and the like.
Special type of dry powder
extinguishers and sand
buckets.
E.
Fires in electrical
equipments.
Chemical Extinguishers of
carbon dioxide and dry
powder type and sand
buckets.
(2) One 9 litres water bucket shall be provided for every 100 sq. m. of the floor area or
part thereof and one 9 litres water type extinguishers shall be provided to six buckets
or part thereof with a minimum of one extinguisher and two buckets per compartment
of the building. Buckets may be dispensed with, provided supply of extinguishers is
double that indicated above.
(3) Acceptable replacements for water buckets and water type extinguishers in
occupancies where Class B fires are anticipated are as under :
Acceptable
Replacement
Buckets of water
Water type
Extinguishers
s
For one
bucket
For three
buckets
For each 9
ltrs. (or 2
gallons)
extinguishers
Dry sand 1 bucket 3 buckets .............
Carbon
dioxide
Extinguishers
3 kg. (or 7
lbs)
9 kg. (or 20
lbs) (In not
less than 2
extinguishers)
.
9 kg. (or 20
lbs)
Dry powder
2 kg. (or 5
lbs)
5 kg. (or 11
lbs) (In one or
more
extinguishers)
.
5 kg. (or 11
lbs)
Foam
extinguishers
9 litres (or 2
gallons)
9 litres (or 2
gallons)
9 litres (or 2
gallons)
(4) The following provisions shall be complied with where Class E fires are
anticipated :-
(a) For rooms containing electrical transformers, switchgears, motor and/or other
electrical apparatus only, not less than two kg. Dry powder or Carbon Dioxide type
extinguishers shall be provided within 15 m. of the apparatus.
(b) Where motors and/or other electrical equipment are installed in room other than
those containing such equipment only, one 5 kg. Dry powder or Carbon Dioxide
extinguisher shall be installed within 15 m. of such equipment in addition to the
requirements as mentioned at (3) and (4) above. For this purpose the same
extinguisher may be deemed to afford protection to all apparatus within 15 m. thereof.
(c) Where electrical motors are installed on platforms, one 2 kg. Dry powder or
Carbon dioxide type extinguisher shall be provided on or below each platform. In case
of a long platform with a number of motors, one extinguisher shall be acceptable as
adequate for every 3 motors on the common platform. The above requirements will be
in addition to the requirements mentioned at Item (3) and (4) above.
(5) The first aid fighting equipments shall be so distributed over the entire floor area
that a person has to travel not more than 15 m. to reach the nearest equipment.
(6) Selection of sites for the installation of first aid fire fighting equipments :
(a) While selecting sites for first aid fire fighting equipments, due consideration shall
be given to the nature of the risk to be covered. The equipments shall be placed in
conspicuous position and shall be readily accessible for immediate use in all parts of
the occupancy. It should always be borne in mind while selecting sites that first aid fire
fighting equipments are intended only for the use on incipient fires and their value may
be negligible if the fire is not extinguished or brought under control in the early stages.
(b) Buckets and extinguishers shall be placed at convenient and easily accessible
locations either on hangers or on stands in such a way that their bottom is 750 mm.
above the floor level.
(7) The operation instructions of the extinguishers shall not be defected or obliterated.
In case the operating instructions are obliterated or have become illegible due to
passage of time fresh transfers of the same shall be obtained from the manufacturers
of the equipments and affixed to the extinguishers.
Schedule II
Equipment to be provided with trailer pump
For light trailer pump of a capacity of 680 litres/minute :-
1 Armoured suction hose of 9 meters length, with wrench.
2 Metal suction strainer.
1 Basket strainer.
1 Two-way suction collecting-head.
1 Suction adopter.
10 Unlined or rubber lined 70 mm. delivery hose of 25 meters length complete
with quick-release couplings.
1 Dividing breaching place.
2 Branch-piece with 15 mm. nozzles.
1 Diffuser nozzles.
1 Standpipe with blank cap.
1 Hydrant key.
4 Collapsible canvas buckets.
1 Fire hook (preventor) with cutting edge.
1 25 mm. manila rope of 30 metres length.
1 Extension ladder of 9 metres length (where necessary).
1 Heavy axe.
1 Spade.
1 Pick axe.
1 Crowbar.
1 Saw.
1 Hurricane lamp.
1 Electric torch.
1 Pair rubber gloves.
For large trailer pump of capacity of 1800 litres/minute.
1 Armoured suction hose of 9 metres length, with wrenches :
1 Metal strainer.
1 Basket Strainer.
1 Three-way suction collecting head.
1 Suction adopter.
14 Unlined or rubber lined 70 mm. delivery hose of 25 metres length complete
with quick release couplings.
1 Dividing breaching place.
4 Branch pipes with one 25 mm., two 20 mm. and one diffuser nozzles.
2 Stand pipes with black caps.
2 Hydrant keys.
6 Colapsible canvas buckets.
1 Coiling hook (preventer) with cutting edge.
1 50 mm. manila rope of 30 meters length.
1 Extension ladder of 9 meters length (where necessary).
1 Heavy axe.
1 Spade.
1 Pick axe.
1 Crowbar.
1 Saw
1 Hurricane lamp.
1 Electric torch.
1 Pair rubber gloves.
Note. - If it appears to the Chief Inspector of Factories that in any factory the
provisions of breathing apparatus and any other emergency device is necessary he
may by order in writing require the occupier to provide suitable breathing apparatus or
the emergency device in addition to the equipment for light trailer pump or large trailer
pump as the case may be.]