Rule 67A, The Factory rules 1962: Water Sealed Gas Holder
The Factory rules 1962 - Rule 67A
Text of rule 67A
Water Sealed Gas Holder
[67A. Water Sealed Gas Holder. - (1) The expression "gas holder" means a
water-sealed gas-holder which has a storage capacity of not less than 141.5 cubic
meters (5000 cf.)
(2) Every gas-holder shall be of adequate material and strength, sound construction
and properly maintained.
(3) Where there is more than one gas-holder in the factory every gasholder shall be
marked in a conspicuous position with a distinguishing number or letter.
(4) Every gasholder shall be thoroughly examined externally by a competent person
at least once in a period of 12 months.
(5) In the case of gasholder of which any lift has been in use for more than two years,
the internal state of the sheeting shall, within one year of the coming into Operation of
these rules and thereafter at least every period of four years, be examined by a
competent person by means of electronic or other accurate devices :
Provided that if the Chief Inspector is satisfied that such electronic or other accurate
devices are not available, he may permit the cutting of samples from the crown and
the sides of the holder :
Provided further that if the above inspection raises a doubt, an internal visual
examination shall be made.
(6) All possible steps shall be taken to prevent or minimise ingress or impurities in the
gasholder.
(7) No gasholder shall be repaired or demolished except under the direct supervision
of a person who by his training and experience and his knowledge of the necessary
precautions against risks of explosion and of person being overcome by gas, is
competent to supervise such work.
(8) (i) All sample discs cut under sub-rule (5) above shall be kept readily available for
inspection.
(ii) A permanent register in Form 9-A duly signed by the occupier or manager shall be
maintained giving the following particulars :
(a) The serial number of the gasholder, vide Rule 3 above and the particulars of
manufacture i.e. maker's name, date of manufacture, capacity, number of lifts,
pressure thrown by holder when full of gas.
(b) The dates of inspections carried out as required under Rules 4 and 5 above and by
whom carried out.
(c) The method of Inspection used.
(d) Date of painting etc.
(e) Nature of repairs and name of person carrying out repairs, and
(f) Remarks.
(iii) The results of examinations by a competent person carried out under sub-rule (4)
and (5) shall be in the Form No. 9-A.
(iv) A copy of the report shall be kept in the register and both the register and the
report shall be readily available for inspection.]
Rule prescribed under sub-section (2) of Section 34
Previous and next
Questions people ask
Is rule 67A of the Factory rules 1962 still in force?
No repeal of the Factory rules 1962 is recorded.