Rule 36, The Rajasthan Cinemas (Regulation) Rules, 1959: Fire Extinguishing Appliances
The Rajasthan Cinemas (Regulation) Rules, 1959 - Rule 36
Text of rule 36
Fire Extinguishing Appliances
36. Fire Extinguishing Appliances. - The following fire extinguishing
appliances shall be provided:-
(1) In the enclosure. - 1[Two liquid chemical extinguishers, one fire
extinguisher using carbon tetrachloride acid, one bucket of sand, two buckets
of water and a damp blanket shall be kept inside the enclosure. A large
sponge shall be kept in one of the buckets of water. One liquid chemical
extinguisher shall also be kept out-side the enclosure.]
In the auditorium. - Four portable fire extinguishers, 20 buckets of water and
a cistern supplying not less than five gallons of water per 100 square feet of
floor area stored.
(2) These appliances shall be so disposed as to be readily available for the
use. The buckets shall have round bottoms and handles and shall be of 2 1/2
to 3 gallons capacity, each to hold not less than 2 gallons of water. They shall
be printed red with the word "Fire" painted on them in large black letters in
English and the 2[XXX] vernacular.
(3) The portable fire extinguishers shall be of soda acid type and of the two
gallon size; they shall be installed at an adequate height from the ground. A
record regarding the maintenance of portable extinguishers shall be kept.
(4) Where a portable fire extinguisher of the chemical combination pressure
type is older than three years or has not been tested previously, it shall be
tested by hydraulic pressure by the Electrical Inspector or by an engineering
firm or mill authorised in this behalf by the licensing authority, to show that it
can withstand for one minute a pressure of 300 lb. per square inch and a
certificate of such test shall be submitted to the licensing authority, Similar
tests shall be repeated once in two years.
(5) At least four stirrup pumps and eight buckets filled with water. If there is
no gallery or first floor in the premises and at least six stirrup pumps and
twelve buckets filled with water if there is a gallery or first floor in the
premises in which case, at least two stirrup pumps and four buckets filled
with water shall be kept in the gallery or first floor.
(6) Attendants and staff be trained in the use of all fire- fighting equipment
maintained in the premises.
(7) The licensee shall —
(i) once in every three months empty the container of each portable fire
extinguisher provided in the licensed premises, clean its nozzles and
working parts, stir the liquids in it and top it up, immediately record the
date of having done so on a slip of paper and paste the same on
the out side of such container,
1 Substituted by No. 3, dated 15-2-1963.
2 Deleted by No. 10, dated 24.5.1982.
(ii) once in every year discharge each portable fire extinguisher
provided in the licensed premises and recharge it and immediately
record the date of such recharge in durable paint on the external
surface of the container of the portable fire extinguisher; and
(iii) Stock at least five refills for the use of the fire- extinguishers.
Previous and next
All provisions of The Rajasthan Cinemas (Regulation) Rules, 1959
Questions people ask
Is rule 36 of the Rajasthan Cinemas (Regulation) Rules, 1959 still in force?
No repeal of the Rajasthan Cinemas (Regulation) Rules, 1959 is recorded.