Rule 117, THE INDIAN ELECTRICITY RULES, 1956: Earthing metal, etc

THE INDIAN ELECTRICITY RULES, 1956 - Rule 117

Text of rule 117

Earthing metal, etc

117. Earthing metal, etc.- (1) All metallic sheaths, coverings, handles, joint broxes, switchgear frames, instrument covers, switch and fuse covers of boxes, all lampholders (unless efficiently protected by an insulated covering made of fire resisting material), and the frames and bedplates of generators, transformers and motors (including portable motors), shall be earthed by connection to an earthing system in the manner prescribed in rule 115. (2) Where cables are provided with a metallic covering constructed and installed in accordance with clause (d) of rule 122, such metallic covering may be used as a means of connection to the earthing system. (3) All conductors of an earthing system shall have conductivity, at all parts and all joints, at least equal to 50 per cent of that of the largest conductor used solely to supply the apparatus, a part of which it is desired to earth. Provided that no conductor of an earthing system shall have a cross-sectional area less than 0.15 sq. cm. except in the case of the earth conductor of a flexible cable used with portable apparatus where the voltage does nor exceed 125 volts, and the cross-sectional area and conductance of the earthcore is not less than that of the largest of the live conductors in the cable. (4) All joints in earth conductors and all joints in the metallic covering of cables shall be properly soldered or otherwise efficiently made. (5) No switch, fuse, or circuit-breaker shall be inserted in any earth conductor. (6) This rule shall not apply (except in the case of portable apparatus) to any system in a mine in which the voltage does not exceed 30 volts. 1[118. Voltage limits- Energy shall not be transmitted into a mine at a voltage exceeding 11000 volts and shall not be used therein at a voltage exceeding 6600 volts. Provided that: (a) Where hand-held portable apparatus is used, the voltage shall not exceed 125 volts; (b) Where electric lighting is used: - (i) In underground mines, the lighting system shall have a mid or neutral point connected with earth and the voltage shall not exceed 125 volts between phases; (ii) On the surface of a mine or in an open cast mine, the voltage may be raised to 250 volts, if the neutral or the mid point of the system is connected with earth and the voltage between the phases does not exceed 250 volts; (c) Where portable hand-lamps are used in underground working of mine, the voltage shall not exceed 30 volts; (d) Where any circuit is used for the remote control or electric interlocking of apparatus, the circuit voltage shall not exceed 30 volts; Provided that in fixed plants, the said voltage may be permitted upto 650 volts, if the bolted type plug is used.] 1. Subs. by GSR 361, dt. 19.3.1983, w.e.f. 7.5.1983. 1[119. Transformers- Where energy is transformed, suitable provision shall be made to guard against danger by reason of the lower voltage apparatus becoming accidentally charged above its normal voltage by leakage from or contact with the higher voltage apparatus.] 1. Subs. by GSR 45, dt. 1.1.1993, w.e.f. 23.1.1993. 120. Switchgear and terminals- Switchgear and all terminals, cable-ends, cable-joints and connections to apparatus shall be totally enclosed and shall be constructed, installed and maintained as to comply with the following requirements: - (a) All parts shall be of mechanical strength sufficient to resist rough usage; (b) All conductors and contact areas shall be of adequate current-carrying capacity and all joints in conductors shall be properly soldered or otherwise efficiently made; (c) The lodgement of any matter likely to diminish the insulation or affect the working of any switchgear shall be prevented; (d) All live parts shall be so protected or enclosed as to prevent persons accidentally coming into contact with them and to prevent danger from arcs, short-circuits, fire, water, gas or oil; (e) Where there may be risk of igniting gas, coal-dust, oil or other inflammable material, all parts shall be so protected as to prevent open sparking; and (f) Every switch or circuit-breaker shall be constructed as to be capable of opening the circuit, if controls and dealing with any short-circuit without danger. 121. Disconnection of supply- (1) Properly constructed switchgear for disconnecting the supply of energy to a mine or oil-field shall be provided 1[***] at a point approved by the Inspector. During the time any cable supplying energy to the mine from the aforesaid switchgear is live, a person authorised to operate the said switchgears shall be available within easy reach thereof. 2[Provided that in the case of gassy coal seam of degree II and degree III, the main mechanical ventilator operator by electricity shall be interlocked with the switchgear so as to automatically disconnect the power supply in the event of stoppage of main mechanical ventilator.] (2) When necessary in the interest of safety, appropriate apparatus suitably placed, shall be provided for disconnecting the supply from every part of a system. (3) Where considered necessary by the Inspector in the interests of safety, the apparatus specified in sub-rule (2) shall be so arranged as to disconnect automatically from the supply any section of the system subjected to a fault. (4) Every motor shall be controlled by switchgear which shall be so arranged as to disconnect the supply from the motor and from all apparatus connected thereto. Such switchgears shall be so placed as to be easily operated by the person authorised to operate the motor. 3[(5) Whenever required by the Inspector the motor shall be controlled by a switchgear to disconnect automatically the supply in the event of conditions of over-current, over-voltage and single phasing.] 1. Omitted by GSR 45, dt. 1.1.1993, w.e.f. 23.1.1993. 2. Ins. by GSR 45, dt. 1.1.1993, w.e.f. 23.1.1993. 3. Ins. by GSR 137, dt. 29.1.1983, w.e.f. 12.2.1983. 122. Cables- All cables, other than flexible cables for portable or transportable apparatus, shall comply with the following requirements:- (a) All such cables (other than the outer conductor of a concentric cable) shall be covered with insulating material and shall be efficiently protected from mechanical damage and supported at sufficiently frequent intervals and in such a manner as to prevent damage to such cables; (b) (i) Except as provided in clause (c), no cables other than concentric cables or two-core or multicore cables protected by a metallic covering or single core cables protected by a metallic covering and which contain all the conductors of a circuit shall be used- (1) Where the voltage exceeds 125 volts, or (2) When an Inspector considers that there risk of igniting gas or coal-dust or other inflammable material, and so directs; (ii) The sheath of metal-sheated cables and the metallic armouring of armoured cables shall be of a thickness not less than that recommended from time to time in the appropriate standard of the 1[Bureau of Indian Standards]; (c) Where a medium voltage direct current system is used, two single core cables may be used for any circuit provided that their metallic coverings are bounded together by earth conductors so placed that the distance between any two consecutive bonds is not greater than 30 metres measured along either cables; (d) The metallic covering of every cable shall be- (i) Electrically and mechanically continuous througout; (ii) Earthed, if it is required by sub-rule (1) of rule 117 to be earthed by a connection to the earthing system of conductivity not less than of the same length of the said metallic covering; (iii) Efficiently protected against corrosion where necessary; (iv) Of a conductivity at all parts and at all joints at least equal to 50 per cent of the conductivity of the largest conductor enclosed by the said metallic covering; and (v) Where there may be risk of igniting gas, coal-dust, or other inflammable material, so constructed as to prevent, as far as practicable, the occurrence of open sparking so as the result of any fault or leakage from live conductors; (e) Cables and conductors where connected to motors, transformers, switch- gear, and other apparatus, shall be installed so that:- (i) They are mechanically protected by securely attaching the metallic covering to the apparatus; and (ii) The insulating material at each cable end is efficiently sealed so as to prevent the diminution of its insulating properties; (f) Where necessary to prevent abrasion or to secure gas-tightness properly constructed glands or bushes shall be provided; (g) Unarmoured cables or conductors shall be conveyed either in metallic pipes or metal casings or suspended from efficient insulators by means of non- conducting materials which will not cut the covering and which will prevent contact with any timbering or metal work. If separate insulated conductors are used, they shall be installed at least 3.75 cm. apart and shall not be brought together except at lamps, switches and fittings. 1. Subs. by GSR 466, dt. 18.7.1991, w.e.f. 17.8.1991. 123. Flexible cables- (1) Flexible cables for portable or transportable apparatus shall be two-core or multi-core (unless required for electric welding), and shall be covered with insulating material which shall be efficiently protected from mechanical injury If flexible metallic covering is used either as the outer conductor of a concentric cable or as a means of protection from mechanical injury, it shall not be used by itself to form an earth conductor for such apparatus, but it may be used for that purpose in conjunction with an earthing core. (2) Every flexible cable intended for use with portable or transportable apparatus shall be connected to the system and to such apparatus by properly constructed connectors. Provided that for high voltage machines a bolted type connector shall be used and the trailing cable shall be suitably anchored at the machine end. (3) At every point where flexible cables are joined to main cables, a 1[circuit breaker] shall be provided which is capable of 1[automatically] disconnecting the supply from such flexible cables. (4) Every flexible cable attached to a portable or transportable machine shall be examined periodically by the person authorised to operate the machine, and if such cable is used underground, it shall be examined at least once in each shift by such person. If such cable is found to be damaged or defective, it shall forthwith be replaced by a cable in good condition. (5) If the voltage of the circuit exceeds low voltage, all flexible cable attached to any transportable apparatus shall be provided with flexible metallic screening or pliable armouring. 2[Provided that this sub-rule shall not apply to flexible cables attached to any transportable apparatus used in open cast mines where reeling and unreeling of such cables is necessary as per design features of the equipment.] (6) All flexible metallic screening or armouring specified in sub-rule (5) shall comply with the provisions of rule 122 (d). Provided that in the case of separately screened flexible cables the conductance of each such screen shall not be less than 25 per cent of that the power conductor and the combined conductance of all such screens shall in no case be less than that of 0.15 sq. cm. copper conductor. (7) Flexible cable exceeding 90 metres in length shall not be used with any portable or transportable apparatus. Provided that such flexible cable when used with coal-cutting machines for long wall operation shall not exceed 180 metres in length. Provided further that the aforesaid cable in case of an open cast mine, when used with 1[electrically operated heavy earth moving machinery] shall not exceed 300 metres in length. (8) Flexible cable, when installed in a mine, shall be efficiently supported and protected from mechanical injury (9) Flexible cables shall not be used with apparatus other than portable or transportable apparatus. (10) Where flexible cables are used they shall be detached or otherwise isolated from the source of supply when not in use, and arrangements shall be made to prevent the energising of such cables by unauthorised persons. 1. Subs. by GSR 466, dt. 18.7.1991, w.e.f. 17.8.1991. 2. Ins. by GSR 137, dt. 12.2.1983. 124. Portable and transportable machines- The person authorised to operate an electrically driven coal-cutter, or other portable or transportable machine, shall not leave the machine while it is in operation and shall, before leaving the area in which such machine is operating, ensure that the supply is disconnected from the flexible cable which supplies the machine. When any such machine is in operation, step shall be taken to ensure that the flexible cable is not dragged along by the machine. 1[Provided that all portable and transportable machines used in underground mines shall operate on remote control from the concerned switchgear with Pilot Core Protection.] 1. Subs. by GSR 45, dt. 1.1.1993, w.e.f. 23.1.1993. 125. Sundry precautions- (1) All apparatus shall be maintained reasonably free from dust, dirt and moisture, and shall be kept clear of obstruction. (2) All apparatus other than portable and transportable apparatus shall be housed in a room, compartment or box so constructed as to protect the contents from damage occasioned by falling material or passing traffic. (3) Inflammable or explosive material shall not be stored in any room, compartment or box containing apparatus, or in the vicinity of any apparatus. (4) Should there be a fault in any circuit, the part affected shall be made dead without delay and shall remain so until the fault has been remedied. (5) While lamps are being changed the supply shall be disconnected. (6) No lamp holder shall be in metallic connection with the guard or other metal work of a portable hand lamp. (7) The following notices, in Hindi and local language of the district, so designed and protected as to be easily legible at all times, shall be exhibited: - (a) At all places where electrical apparatus is in use, a notice forbidding unauthorized person to operate or otherwise interfere with such apparatus; (b) At those places in the interior or at the surface of the mine where a telephone or other means of communication is provided, a notice giving full instructions to persons authorized to effect the disconnection, at the surface of the mine, of the supply of energy to the mine. (8) All apparatus, including portable and transportable apparatus, shall be operated only by those persons who are authorised for the purpose. (9) Where a plug-and-socket-coupling other than of bolted type is used with flexible cables, and electrical inter-lock or other approved device shall be provided to prevent the opening of the coupling while the conductors are live. 1[126. Precautions where gas exists- (1) In any part of a coal-seam of the first degree gassiness- (a) All cables shall be constructed, installed, protected, operated and maintained in such a manner as to prevent risk of open sparking; (b) At any place which lies in-bye of the last ventilation connection, all 2[signalling or telecommunication and remote control] circuits shall be so constructed, installed, protected, operated and maintained as to be intrinsically safe; (c) All apparatus including portable and transportable apparatus including lighting fittings used at any place which lies in bye of the last ventilation connection shall be flame-proof. (2) At any place which lies in any part of a coal-seam of second and third degree gassiness- (a) All 2[signalling, telecommunication and remote control] circuits shall be so constructed, installed, protected, operated and maintained as to be intrinsically safe; (b) All cables shall be constructed, installed, protected, operated and maintained in such a manner as to prevent risk of open sparking; (c) All apparatus, including portable and transportable apparatus used at any place within 90 metres of any working face or goaf in case of a second degree gassymine and within 270 metres of any working face or goaf in case of third degree gassymine or at any place which lies in-bye of the last ventilation connection or in ar-y return airways shall be flame-proof; (d) All electric lamps shall be enclosed in flame-proof enclosures. (3) In any oil mine or oil-field, at any place within the Danger Areas, - (a) All 3[signalling and telecommunication and remote control] circuits shall be so constructed, installed, operated, protected and maintained as to be instrinsically safe; (b) All cables shall be so constructed, installed, operated and maintained as to prevent risk of open sparking; (c) All apparatus including portable and transportable apparatus shall be flame-proof; (d) All electric lamps shall be enclosed in flame-proof enclosures. (4) In any coal-seam of degree second and degree third gassiness or the danger zone of oil-mine the supply shall be discontinued, - (a) Immediately, if open sparking occurs; (b) During the period required for examination or adjustment of the apparatus, which would necessitate the exposing of any part liable to open sparking; (c) The supply shall not be reconnected until the apparatus has been examined by the electrical supervisor or one of his duly appointed assistants until the defect, if any, has been remedied or the necessary adjustment made; (d) A flame safety lamp shall be provided and maintained in a state of continuous illumination near an apparatus (including portable or transportable apparatus) which remains energised and where the appearance of the flame of such safety lamps indicates the presence of inflammable gas, the supply to all apparatus in the vicinity shall be immediately disconnected and the incident reported forthwith to an official of the mine; 4[and such apparatus shall be interlocked with the controlling switch in such a manner as to disconnect power supply automatically in the event of percentage of inflammable gas exceeding one and one quarter in that particular district;] Provided that where 5[apparatus] for automatic detection of the percentage of inflammable gas or vapur are employed in addition to the flame safety lamps, such 5[apparatus] shall be approved by the Inspector of Mines and maintained perfect order. (5) (i) In any part of a coal-seam of any degree of gassiness or in 6[any hazardous] area of an oil-mine, if the presence of inflammable gas in the general body of air is found any time to exceed one and one quarter 7[per cent], the supply of energy shall be immediately disconnected from all cables and apparatus in the area and the supply shall not be reconnected so long as the percentage of inflammable gas remains in excess of one and one quarter 7[per cent]. 8[In an oil mine where concentration of inflammable gas exceed 20% of its lowest explosive limit, the supply of electric energy shall be cutoff immediately from all cables and apparatus lying within 30 metres of the installation and all sources of ignition shall also be removed from the said area and normal work shall not be resumed unless the area is made gas-free;] 9[Provided that such disconnection shall no apply to intrinsically safe environmental monitoring scientific instruments.] (ii) Any such disconnection or reconnection of the supply shall be noted in the log sheet which shall be maintained -in the form set out in Annexure-XII and shall be reported to the Inspector. (6) The provisions of this rule shall apply to any metalliferous mine which may be notified by the Inspector of Mines ii inflammable gas occurs or if the Inspector of Mines is of the opinion that inflammable gas is likely to occur in such mine. Explanation- For the purpose of this rule, - (1) The expression coal-seam of first degree gassiness, coal-seam of second degree gassiness’, ‘coal-seam of third degree gassiness’ and ‘flame-proof apparatus’, shall have the meanings respectively assigned to them in the Coal Mines Regulations, 1957. (2) The following areas in an oil-mine or oil-field shall be known as 6[hazardous areas], namely:- (a) An area of not less than 90 metres around an oil-well where a blow-out has occurred or is likely to occur, as may be designated by the engineer-in- charge or the senior most official present at the site; (b) An area within 90 metres of an oil-well which is being tested by open flow; (c) An area within 15 metres of- (i) A producing well-head or any point of open discharge of the crude therefrom or other point where emission of 10[hazardous atmosphere] is normally likely to arise, or (ii) Any wildcat or exploration well-head being drilled in an area where abnormal pressure conditions are known to exist, or (iii) Any exploration or interspaced well-head being drilled in the area where abnormal pressure conditions are known to exist; or (d) Any area within 4.5 metres of- (i) Any producing well-head where a closed system of production is employed such as to prevent the emission accumulation in the area in normal circumstances of a 10[hazardous atmosphere]; or (ii) Exploration or interspaced well-head being drilled in an area where the pressure conditions are normal and where the system of drilling employed includes adequate measures for the prevention in normal circumstances of emission or accumulation within the area of a 10[hazardous atmosphere]; or (iii) An oil-well which is being tested other than by open flow. Explanation- For the purposes of clause (d) 10[hazardous atmosphere] means an atmosphere containing any inflammable gases or vapours in a concentration capable of ignition. 11[(e) All appliances, equipments and machinery that are or may be used in zone 0, zones 1 and 2 hazardous areas shall be of such type, standard and make as approved by the Inspector by a general or special order in writing. Explanation- (i) “Zone 0 hazardous area” means “an area in which hazardous atmosphere is continuously present.” (ii) “Zone 1 hazardous area” means “an area in which hazardous atmosphere is likely to occur under normal operating conditions”. (iii) “Zone 2 hazardous area” means “an area in which hazardous atmosphere is likely to occur only under abnormal operating conditions”.] 1. Subs. by GSR 466, dt. 18.7.1991, w.e.f. 17.8.1991. 2. Subs by GSR 466, dt. 18.7.1991, w.e.f. 17.8.1991. 3. Subs by GSR 466, dt. 18.7.1991, w.e.f. 17.8.1991. 4. Added by GSR 45, dt. 1.1.1993, w.e.f. 23.1.1993 5. Subs. by GSR 45, dt. 1.1.1993, w.e.f. 23.1.1993. 6. Subs. by GSR 466, dt. 18.7.1991, w.e.f. 17.8.1991. 7. Added by GSR 466, dt. 18.7.1991, w.e.f. 17.8.1991. 8. Ins. by GSR 45, dt. 1.1.1993, w.e.f. 23.1.1993. 9.. Ins. by GSR 466, dt. 18.7.1991, w.e.f. 17.8.1991. 10. Subs. by GSR 253, dt. 19.2.1981, w.e.f. 7.4.1981. 11. Ins. by GSR 466, dt. 18.7.1991, w.e.f. 17.8.1991 127. Shot-firing- (1) When shot-firing is in progress adequate precautions shall be taken to protect apparatus and conductors other than those used for shot-firing from injury. (2) Current from lighting or power circuits shall not be used for firing shots. (3) The provisions of rule 123 shall apply in regard to the covering and protection of shot-firing cables, and adequate precautions shall be taken to prevent such cable touching other cables and apparatus. 128. Signalling- Where electrical signalling is used- (a) Adequate precautions shall be taken to prevent signal and telephone wires coming into contact with other cables and apparatus; (b) The voltage used in any one circuit shall not exceed 30 volts; and (c) Contact-makers shall be so constructed as to prevent the accident closing of the circuit. 1[(d) Bare conductors, where used shall be installed in suitable insulators.] 1. Ins. by GSR 45, dt. 1.1.1993, w.e.f. 23.1.1993. 129. Haulage- Haulage by electric locomotives on the overhead trolley-wire system, at medium or low voltage, and haulage by storage battery locomotives may be used with the prior consent in writing of the Inspector, and subject to such conditions as he may impose in the interests of safety 130. Earthing of neutral points- Where the voltage of an alternating current system exceeds 30 volts, the neutral or mid-point shall be earthed by connection to an earthing system in the manner prescribed in rule 115. Provided that when the system concerned is required for blasting and signalling purposes, the provisions of this rule shall not apply. 1[Provided further that in case of unearthed neutral system adequate protection shall be provided with the approval of the Inspector.] 1. Ins. by GSR 45, dt. 1.1.1993, w.e.f. 23.1.1993. 1[131. Supervision- 1. Subs by GSR 253, dt. 19.2.1983, w.e.f. 7.3.1983. (1) (i) One or more electrical supervisors as directed by the Inspector shall be appointed in writing by the owner, agent or manager of a mine or by the agent or the owner, of one or more wells in an oil field to supervise the installation. (ii) The electrical supervisor so appointed shall be the person holding a valid Electrical Supervisor’s Certificate of Competency, covering mining installation issued under sub-rule (1) of rule 45. (iii) If the Inspector considers necessary for the compliance with the duties specified in this rule, he may direct the owner or agent of the mine to appoint one or more electricians who shall be persons holding licence under sub-rule (1) of rule 45. (2) Every person appointed to operate, supervise, examine or adjust any apparatus shall be competent to undertake the work which he is required to carryout as directed by the engineer. (3) The electrical supervisor shall be responsible for the proper performance of the following duties, by himself or by electrician appointed under sub-rule (1):- (a) Through examination of all apparatus (including the testing of earth conductors and metallic coverings for continuity) as often as may be necessary to prevent danger; (b) Examination and testing of all new apparatus, and of all apparatus, re- erected in the mine before it is put into service in a new position. (4) In the absence of any electrical supervisor for more than three days, the owner, agent or manager of the mine or the agent or owner of one or more oil- wells in an oil-field, shall appoint in writing a substitute electrical supervisor. (5) (i) The electrical supervisor or the substitute electrical supervisor appointed under sub-rule (4) to replace him shall be personally responsible for the maintenance at the mine or oil-field, of a long book made up of the daily log sheets prepared in the form set out in Annexure-XII. (ii) The results of all tests carried out in accordance with the provisions of sub-rule (3) shall be recorded in the log-sheets prepared in the form set out in Annexure-XII.] 132. Exemptions- The provisions of rules 110 to 128 both inclusive and rule 131 shall not apply in any case, where, on grounds of emergency or special circumstances, exemption is obtained from the Inspector. In granting any such exemption the Inspector may prescribe such conditions as he thinks fit. CHAPTER XI MISCELLANEOUS 133. Relaxation by Government- (1) The State Government, or where mine, oil-fields or railways or works executed for or on behalf of the Central Government, are affected, the Central Government, may by order in writing, direct that any of the provisions of rules in Chapter IV other than rules 44A and 46, and all rules in Chapters V, VI, VII, VIII and IX shall be relaxed generally or in particular case to such extent and subject to such conditions as it may think fit. (2) The Central Government may, by order in writing, direct that any of the provisions of Chapter X of these rules shall be relaxed in any particular case to such an extent and subject to such conditions as it may think fit. 134. Relaxation by Inspector- The Inspector, may, by order in writing, direct that any of the provisions of rules 44, 1[50 (1)(a), (b) and (d), 50 A (2), 51 (1)], 61 (2), 63, 64(2), 65,71 to 73 (inclusive), 76 to 80 (inclusive), go, 2[118], 119(l)(a), 123(5), 123(17), 2[123(9) and 130], shall be relaxed in any case to such extent and subject to suit conditions as he may think fit. (2) Where the voltage of any system does not exceed 125 volts the Inspector may, by order in writing, direct that any of the provisions of rules 29 to 34 (inclusive), 36 to 39 (inclusive), 83, 92, 94 to 107 (inclusive) shall, in addition to the rules specified in Sub-rule (1), be relaxed as regards such systems to such extent and subject to such conditions as he may think fit. (3) Every relaxation so directed shall be reported forthwith to, and shall be subject to disallowance or revision by, the State Government, or where the relaxation affects mines, oil-fields or railways, by the Central Government. 1. Subs by GSR 45, dt. 1.1.1993, w.e.f. 23.1.1993. 2. Subs by GSR 466, dt. 18.7.1991, w.e.f. 17.8.1991. 135. Supply and use of energy by non-licensees and others- Where any person other than a non-licensee is supplied with energy by a non-licensee or other person or has his premises for the time being connected to the conductors or plant of a non-licensee or other person, or himself generates energy and uses such energy or part thereof, such person shall be deemed to be a consumer for the purposes of rules 9, 10, 29 to 33 (inclusive), 45 to 70 (inclusive), 87 and 142 and non-licensee or other person shall be subject to all the liabilities imposed on a licensee by these rules. 136. Responsibility of Agents and Managers- Where any person is responsible for the observance of any of these rules, every agent and manager of such person shall also be responsible for such observance in respect of matters under their respective controls. 137. Mode of entry- All persons entering in pursuance of the Act or these rules, any building which is used as a human dwelling or a place of worship shall, in making such entry have due regard so far as may be compatible with the exigencies of the purpose for which such entry is made, to the social and religious usages or the occupant of the building entered. 138. Penalty for breaking seal- Where, in contravention of rule 56 any seal referred to in that rule is broken- (a) The person breaking the seal shall be punishable with fine which may extend to two hundred rupees; and (b) The consumer when he has not himself broken the seal shall be punishable with fine which may extend to fifty rupees unless he proves that he used all reasonable means in his power to ensure that the seal should not be broken. 1[138A. Penality for breach of rule 44A- Where, in contravention of rule 44A, any person responsible for the generation, transformation, transmission, conversion, distribution, supply or use of energy fails to report to the Inspector and other authorities concerned the occurrence of accidents, such person shall be punishable with fine which may extend to three hundred rupees. 1. Ins. by GSR 523, dt. 28.3.1966, w.e.f. 9.4.1966. 139. Penalty for breach of rule 45- Where any electrical installation work of the nature specified in sub-rule (1) of rule 45 has been carried out otherwise than-- (a) Under the direct supervision of a person holding a certificate of competency issued by the State Government under that rules; and (b) In the absence of any applicable exemption under the proviso to sub-rule of that rule, by an electrical contractor licensed by the State Government in this behalf, The consumer owner or occupier, the contractor (if any) or the person through whom the work is being or was carried out and the person under whose immediate supervision the work is being or was carried out, shall each be punishable with fine which may extend to three hundred rupees. 1[140. Penalty for breach of rule 82- (a) Where no notice is given under rule 82(l) or the amount of estimate as demanded under rule 82(2) is not deposited, both the persons proposing and the contractor engaged for erecting a new building or structure whether permanent or temporary or for making in or upon an building or structure any permanent or temporary additions or alterations, shall be deemed to have committed a breach of rule 82(l) and shall be punishable with a fine which may extend to three hundred rupees. (b) If any person commences or continues any work in contravention of rule 82(3), in or upon any such building, structure, flood bank, road or carries out addition or alteration thereto, the person contravening the same shall be punishable with a fine which may extend to three hundred rupees. In addition to this the supplier shall, after obtaining the concurrence of the Inspector discontinue the supply, if any, to such building, structure, flood bank, or road etc. but only after giving forty-eight hours notice to the person concerned in writing of disconnection of supply and shall not commence the supply until he and the inspector are satisfied that the cause has been removed.] 1. Subs by GSR 529, dt. 11.7.1986, w.e.f. 19.7.1986. 1[140A. Penalty for breach of rule 77,79 or 80- Where a person is responsible for any construction which is or which results in contravention of the provisions of rule 77, 79 or 80 he and the contractor whom he employs shall be punishable with a fine which may extend to three hundred rupees, and in the case of continuing breach, with a further daily fine which may extend to fifty rupees. 1. Ins. by GSR 1723, dt. 21.11.1977, w.e.f. 31.12.1977. 141. Penalty for breach of rules- Any person other than an Inspector or any officer appointed to assist the Inspector who being responsible for the observance of any of these rules commits a breach thereof, shall be punishable for every such breach with fine which may extend to three hundred rupees, and in the case of a continuing breach with a further fine which may extend to fifty rupees, for every day after first during which the breach has continued. 142. Application of rules- Subject to the provisions of sub-section (2) of section 58, these rules shall be binding on all persons, companies and undertakings to whom licences have been granted or with whom agreements have been made by or with the sanction of Government for the supply or use of electricity before the commencement of the Act. 143. Repeal- The Indian Electricity Rules, 1937, are hereby repealed. Provided that any order made, notification issued or anything done or any action taken under any of the said rules shall be deemed to have been made, issued, done or taken under the corresponding provisions of the rules.

Previous and next

All provisions of THE INDIAN ELECTRICITY RULES, 1956

Questions people ask

Is rule 117 of THE INDIAN ELECTRICITY RULES, 1956 still in force?

No repeal of the INDIAN ELECTRICITY RULES, 1956 is recorded.