Rule 117, THE INDIAN ELECTRICITY RULES, 1956: Earthing metal, etc
THE INDIAN ELECTRICITY RULES, 1956 - Rule 117
Text of rule 117
Earthing metal, etc
117. Earthing metal, etc.-
(1) All metallic sheaths, coverings, handles, joint broxes, switchgear frames,
instrument covers, switch and fuse covers of boxes, all lampholders (unless
efficiently protected by an insulated covering made of fire resisting material), and
the frames and bedplates of generators, transformers and motors (including
portable motors), shall be earthed by connection to an earthing system in the
manner prescribed in rule 115.
(2) Where cables are provided with a metallic covering constructed and
installed in accordance with clause (d) of rule 122, such metallic covering may be
used as a means of connection to the earthing system.
(3) All conductors of an earthing system shall have conductivity, at all parts
and all joints, at least equal to 50 per cent of that of the largest conductor used
solely to supply the apparatus, a part of which it is desired to earth.
Provided that no conductor of an earthing system shall have a cross-sectional
area less than 0.15 sq. cm. except in the case of the earth conductor of a flexible
cable used with portable apparatus where the voltage does nor exceed 125 volts,
and the cross-sectional area and conductance of the earthcore is not less than
that of the largest of the live conductors in the cable.
(4) All joints in earth conductors and all joints in the metallic covering of
cables shall be properly soldered or otherwise efficiently made.
(5) No switch, fuse, or circuit-breaker shall be inserted in any earth conductor.
(6) This rule shall not apply (except in the case of portable apparatus) to any
system in a mine in which the voltage does not exceed 30 volts.
1[118. Voltage limits- Energy shall not be transmitted into a mine at a voltage
exceeding 11000 volts and shall not be used therein at a voltage exceeding 6600
volts.
Provided that:
(a) Where hand-held portable apparatus is used, the voltage shall not exceed
125 volts;
(b) Where electric lighting is used: -
(i) In underground mines, the lighting system shall have a mid or neutral
point connected with earth and the voltage shall not exceed 125 volts between
phases;
(ii) On the surface of a mine or in an open cast mine, the voltage may be
raised to 250 volts, if the neutral or the mid point of the system is connected with
earth and the voltage between the phases does not exceed 250 volts;
(c) Where portable hand-lamps are used in underground working of mine, the
voltage shall not exceed 30 volts;
(d) Where any circuit is used for the remote control or electric interlocking of
apparatus, the circuit voltage shall not exceed 30 volts;
Provided that in fixed plants, the said voltage may be permitted upto 650 volts, if
the bolted type plug is used.]
1. Subs. by GSR 361, dt. 19.3.1983, w.e.f. 7.5.1983.
1[119. Transformers- Where energy is transformed, suitable provision shall be
made to guard against danger by reason of the lower voltage apparatus
becoming accidentally charged above its normal voltage by leakage from or
contact with the higher voltage apparatus.]
1. Subs. by GSR 45, dt. 1.1.1993, w.e.f. 23.1.1993.
120. Switchgear and terminals- Switchgear and all terminals, cable-ends,
cable-joints and connections to apparatus shall be totally enclosed and shall be
constructed, installed and maintained as to comply with the following
requirements: -
(a) All parts shall be of mechanical strength sufficient to resist rough usage;
(b) All conductors and contact areas shall be of adequate current-carrying
capacity and all joints in conductors shall be properly soldered or otherwise
efficiently made;
(c) The lodgement of any matter likely to diminish the insulation or affect the
working of any switchgear shall be prevented;
(d) All live parts shall be so protected or enclosed as to prevent persons
accidentally coming into contact with them and to prevent danger from arcs,
short-circuits, fire, water, gas or oil;
(e) Where there may be risk of igniting gas, coal-dust, oil or other inflammable
material, all parts shall be so protected as to prevent open sparking; and
(f) Every switch or circuit-breaker shall be constructed as to be capable of
opening the circuit, if controls and dealing with any short-circuit without danger.
121. Disconnection of supply-
(1) Properly constructed switchgear for disconnecting the supply of energy to
a mine or oil-field shall be provided 1[***] at a point approved by the Inspector.
During the time any cable supplying energy to the mine from the aforesaid
switchgear is live, a person authorised to operate the said switchgears shall be
available within easy reach thereof.
2[Provided that in the case of gassy coal seam of degree II and degree III, the
main mechanical ventilator operator by electricity shall be interlocked with the
switchgear so as to automatically disconnect the power supply in the event of
stoppage of main mechanical ventilator.]
(2) When necessary in the interest of safety, appropriate apparatus suitably
placed, shall be provided for disconnecting the supply from every part of a
system.
(3) Where considered necessary by the Inspector in the interests of safety,
the apparatus specified in sub-rule (2) shall be so arranged as to disconnect
automatically from the supply any section of the system subjected to a fault.
(4) Every motor shall be controlled by switchgear which shall be so arranged
as to disconnect the supply from the motor and from all apparatus connected
thereto. Such switchgears shall be so placed as to be easily operated by the
person authorised to operate the motor.
3[(5) Whenever required by the Inspector the motor shall be controlled by a
switchgear to disconnect automatically the supply in the event of conditions of
over-current, over-voltage and single phasing.]
1. Omitted by GSR 45, dt. 1.1.1993, w.e.f. 23.1.1993.
2. Ins. by GSR 45, dt. 1.1.1993, w.e.f. 23.1.1993.
3. Ins. by GSR 137, dt. 29.1.1983, w.e.f. 12.2.1983.
122. Cables- All cables, other than flexible cables for portable or transportable
apparatus, shall comply with the following requirements:-
(a) All such cables (other than the outer conductor of a concentric cable) shall
be covered with insulating material and shall be efficiently protected from
mechanical damage and supported at sufficiently frequent intervals and in such a
manner as to prevent damage to such cables;
(b) (i) Except as provided in clause (c), no cables other than concentric
cables or two-core or multicore cables protected by a metallic covering or single
core cables protected by a metallic covering and which contain all the conductors
of a circuit shall be used-
(1) Where the voltage exceeds 125 volts, or
(2) When an Inspector considers that there risk of igniting gas or coal-dust or
other inflammable material, and so directs;
(ii) The sheath of metal-sheated cables and the metallic armouring of
armoured cables shall be of a thickness not less than that recommended from
time to time in the appropriate standard of the 1[Bureau of Indian Standards];
(c) Where a medium voltage direct current system is used, two single core
cables may be used for any circuit provided that their metallic coverings are
bounded together by earth conductors so placed that the distance between any
two consecutive bonds is not greater than 30 metres measured along either
cables;
(d) The metallic covering of every cable shall be-
(i) Electrically and mechanically continuous througout;
(ii) Earthed, if it is required by sub-rule (1) of rule 117 to be earthed by a
connection to the earthing system of conductivity not less than of the same
length of the said metallic covering;
(iii) Efficiently protected against corrosion where necessary;
(iv) Of a conductivity at all parts and at all joints at least equal to 50 per cent of
the conductivity of the largest conductor enclosed by the said metallic covering;
and
(v) Where there may be risk of igniting gas, coal-dust, or other inflammable
material, so constructed as to prevent, as far as practicable, the occurrence of
open sparking so as the result of any fault or leakage from live conductors;
(e) Cables and conductors where connected to motors, transformers, switch-
gear, and other apparatus, shall be installed so that:-
(i) They are mechanically protected by securely attaching the metallic
covering to the apparatus; and
(ii) The insulating material at each cable end is efficiently sealed so as to
prevent the diminution of its insulating properties;
(f) Where necessary to prevent abrasion or to secure gas-tightness properly
constructed glands or bushes shall be provided;
(g) Unarmoured cables or conductors shall be conveyed either in metallic
pipes or metal casings or suspended from efficient insulators by means of non-
conducting materials which will not cut the covering and which will prevent
contact with any timbering or metal work. If separate insulated conductors are
used, they shall be installed at least 3.75 cm. apart and shall not be brought
together except at lamps, switches and fittings.
1. Subs. by GSR 466, dt. 18.7.1991, w.e.f. 17.8.1991.
123. Flexible cables-
(1) Flexible cables for portable or transportable apparatus shall be two-core or
multi-core (unless required for electric welding), and shall be covered with
insulating material which shall be efficiently protected from mechanical injury If
flexible metallic covering is used either as the outer conductor of a concentric
cable or as a means of protection from mechanical injury, it shall not be used by
itself to form an earth conductor for such apparatus, but it may be used for that
purpose in conjunction with an earthing core.
(2) Every flexible cable intended for use with portable or transportable
apparatus shall be connected to the system and to such apparatus by properly
constructed connectors.
Provided that for high voltage machines a bolted type connector shall be used
and the trailing cable shall be suitably anchored at the machine end.
(3) At every point where flexible cables are joined to main cables, a 1[circuit
breaker] shall be provided which is capable of 1[automatically] disconnecting the
supply from such flexible cables.
(4) Every flexible cable attached to a portable or transportable machine shall
be examined periodically by the person authorised to operate the machine, and if
such cable is used underground, it shall be examined at least once in each shift
by such person. If such cable is found to be damaged or defective, it shall
forthwith be replaced by a cable in good condition.
(5) If the voltage of the circuit exceeds low voltage, all flexible cable attached
to any transportable apparatus shall be provided with flexible metallic screening
or pliable armouring.
2[Provided that this sub-rule shall not apply to flexible cables attached to any
transportable apparatus used in open cast mines where reeling and unreeling of
such cables is necessary as per design features of the equipment.]
(6) All flexible metallic screening or armouring specified in sub-rule (5) shall
comply with the provisions of rule 122 (d).
Provided that in the case of separately screened flexible cables the conductance
of each such screen shall not be less than 25 per cent of that the power
conductor and the combined conductance of all such screens shall in no case be
less than that of 0.15 sq. cm. copper conductor.
(7) Flexible cable exceeding 90 metres in length shall not be used with any
portable or transportable apparatus.
Provided that such flexible cable when used with coal-cutting machines for long
wall operation shall not exceed 180 metres in length.
Provided further that the aforesaid cable in case of an open cast mine, when
used with 1[electrically operated heavy earth moving machinery] shall not exceed
300 metres in length.
(8) Flexible cable, when installed in a mine, shall be efficiently supported and
protected from mechanical injury
(9) Flexible cables shall not be used with apparatus other than portable or
transportable apparatus.
(10) Where flexible cables are used they shall be detached or otherwise
isolated from the source of supply when not in use, and arrangements shall be
made to prevent the energising of such cables by unauthorised persons.
1. Subs. by GSR 466, dt. 18.7.1991, w.e.f. 17.8.1991.
2. Ins. by GSR 137, dt. 12.2.1983.
124. Portable and transportable machines- The person authorised to operate
an electrically driven coal-cutter, or other portable or transportable machine, shall
not leave the machine while it is in operation and shall, before leaving the area in
which such machine is operating, ensure that the supply is disconnected from the
flexible cable which supplies the machine. When any such machine is in
operation, step shall be taken to ensure that the flexible cable is not dragged
along by the machine.
1[Provided that all portable and transportable machines used in
underground mines shall operate on remote control from the concerned
switchgear with Pilot Core Protection.]
1. Subs. by GSR 45, dt. 1.1.1993, w.e.f. 23.1.1993.
125. Sundry precautions-
(1) All apparatus shall be maintained reasonably free from dust, dirt and
moisture, and shall be kept clear of obstruction.
(2) All apparatus other than portable and transportable apparatus shall be
housed in a room, compartment or box so constructed as to protect the contents
from damage occasioned by falling material or passing traffic.
(3) Inflammable or explosive material shall not be stored in any room,
compartment or box containing apparatus, or in the vicinity of any apparatus.
(4) Should there be a fault in any circuit, the part affected shall be made dead
without delay and shall remain so until the fault has been remedied.
(5) While lamps are being changed the supply shall be disconnected.
(6) No lamp holder shall be in metallic connection with the guard or other
metal work of a portable hand lamp.
(7) The following notices, in Hindi and local language of the district, so
designed and protected as to be easily legible at all times, shall be exhibited: -
(a) At all places where electrical apparatus is in use, a notice forbidding
unauthorized person to operate or otherwise interfere with such apparatus;
(b) At those places in the interior or at the surface of the mine where a
telephone or other means of communication is provided, a notice giving full
instructions to persons authorized to effect the disconnection, at the surface of
the mine, of the supply of energy to the mine.
(8) All apparatus, including portable and transportable apparatus, shall be
operated only by those persons who are authorised for the purpose.
(9) Where a plug-and-socket-coupling other than of bolted type is used with
flexible cables, and electrical inter-lock or other approved device shall be
provided to prevent the opening of the coupling while the conductors are live.
1[126. Precautions where gas exists-
(1) In any part of a coal-seam of the first degree gassiness-
(a) All cables shall be constructed, installed, protected, operated and
maintained in such a manner as to prevent risk of open sparking;
(b) At any place which lies in-bye of the last ventilation connection, all
2[signalling or telecommunication and remote control] circuits shall be so
constructed, installed, protected, operated and maintained as to be intrinsically
safe;
(c) All apparatus including portable and transportable apparatus including
lighting fittings used at any place which lies in bye of the last ventilation
connection shall be flame-proof.
(2) At any place which lies in any part of a coal-seam of second and third
degree gassiness-
(a) All 2[signalling, telecommunication and remote control] circuits shall be so
constructed, installed, protected, operated and maintained as to be intrinsically
safe;
(b) All cables shall be constructed, installed, protected, operated and
maintained in such a manner as to prevent risk of open sparking;
(c) All apparatus, including portable and transportable apparatus used at any
place within 90 metres of any working face or goaf in case of a second degree
gassymine and within 270 metres of any working face or goaf in case of third
degree gassymine or at any place which lies in-bye of the last ventilation
connection or in ar-y return airways shall be flame-proof;
(d) All electric lamps shall be enclosed in flame-proof enclosures.
(3) In any oil mine or oil-field, at any place within the Danger Areas, -
(a) All 3[signalling and telecommunication and remote control] circuits shall be
so constructed, installed, operated, protected and maintained as to be
instrinsically safe;
(b) All cables shall be so constructed, installed, operated and maintained as
to prevent risk of open sparking;
(c) All apparatus including portable and transportable apparatus shall be
flame-proof;
(d) All electric lamps shall be enclosed in flame-proof enclosures.
(4) In any coal-seam of degree second and degree third gassiness or the
danger zone of oil-mine the supply shall be discontinued, -
(a) Immediately, if open sparking occurs;
(b) During the period required for examination or adjustment of the apparatus,
which would necessitate the exposing of any part liable to open sparking;
(c) The supply shall not be reconnected until the apparatus has been
examined by the electrical supervisor or one of his duly appointed assistants until
the defect, if any, has been remedied or the necessary adjustment made;
(d) A flame safety lamp shall be provided and maintained in a state of
continuous illumination near an apparatus (including portable or transportable
apparatus) which remains energised and where the appearance of the flame of
such safety lamps indicates the presence of inflammable gas, the supply to all
apparatus in the vicinity shall be immediately disconnected and the incident
reported forthwith to an official of the mine; 4[and such apparatus shall be
interlocked with the controlling switch in such a manner as to disconnect power
supply automatically in the event of percentage of inflammable gas exceeding
one and one quarter in that particular district;]
Provided that where 5[apparatus] for automatic detection of the percentage of
inflammable gas or vapur are employed in addition to the flame safety lamps,
such 5[apparatus] shall be approved by the Inspector of Mines and maintained
perfect order.
(5) (i) In any part of a coal-seam of any degree of gassiness or in 6[any
hazardous] area of an oil-mine, if the presence of inflammable gas in the general
body of air is found any time to exceed one and one quarter 7[per cent], the
supply of energy shall be immediately disconnected from all cables and
apparatus in the area and the supply shall not be reconnected so long as the
percentage of inflammable gas remains in excess of one and one quarter 7[per
cent].
8[In an oil mine where concentration of inflammable gas exceed 20% of its lowest
explosive limit, the supply of electric energy shall be cutoff immediately from all
cables and apparatus lying within 30 metres of the installation and all sources of
ignition shall also be removed from the said area and normal work shall not be
resumed unless the area is made gas-free;]
9[Provided that such disconnection shall no apply to intrinsically safe
environmental monitoring scientific instruments.]
(ii) Any such disconnection or reconnection of the supply shall be noted in the
log sheet which shall be maintained -in the form set out in Annexure-XII and shall
be reported to the Inspector.
(6) The provisions of this rule shall apply to any metalliferous mine which may
be notified by the Inspector of Mines ii inflammable gas occurs or if the Inspector
of Mines is of the opinion that inflammable gas is likely to occur in such mine.
Explanation- For the purpose of this rule, -
(1) The expression coal-seam of first degree gassiness, coal-seam of second
degree gassiness’, ‘coal-seam of third degree gassiness’ and ‘flame-proof
apparatus’, shall have the meanings respectively assigned to them in the Coal
Mines Regulations, 1957.
(2) The following areas in an oil-mine or oil-field shall be known as
6[hazardous areas], namely:-
(a) An area of not less than 90 metres around an oil-well where a blow-out
has occurred or is likely to occur, as may be designated by the engineer-in-
charge or the senior most official present at the site;
(b) An area within 90 metres of an oil-well which is being tested by open flow;
(c) An area within 15 metres of-
(i) A producing well-head or any point of open discharge of the crude
therefrom or other point where emission of 10[hazardous atmosphere] is normally
likely to arise, or
(ii) Any wildcat or exploration well-head being drilled in an area where
abnormal pressure conditions are known to exist, or
(iii) Any exploration or interspaced well-head being drilled in the area where
abnormal pressure conditions are known to exist; or
(d) Any area within 4.5 metres of-
(i) Any producing well-head where a closed system of production is
employed such as to prevent the emission accumulation in the area in normal
circumstances of a 10[hazardous atmosphere]; or
(ii) Exploration or interspaced well-head being drilled in an area where the
pressure conditions are normal and where the system of drilling employed
includes adequate measures for the prevention in normal circumstances of
emission or accumulation within the area of a 10[hazardous atmosphere]; or
(iii) An oil-well which is being tested other than by open flow.
Explanation- For the purposes of clause (d) 10[hazardous atmosphere] means an
atmosphere containing any inflammable gases or vapours in a concentration
capable of ignition.
11[(e) All appliances, equipments and machinery that are or may be used in
zone 0, zones 1 and 2 hazardous areas shall be of such type, standard and
make as approved by the Inspector by a general or special order in writing.
Explanation- (i) “Zone 0 hazardous area” means “an area in which hazardous
atmosphere is continuously present.”
(ii) “Zone 1 hazardous area” means “an area in which hazardous atmosphere
is likely to occur under normal operating conditions”.
(iii) “Zone 2 hazardous area” means “an area in which hazardous atmosphere
is likely to occur only under abnormal operating conditions”.]
1. Subs. by GSR 466, dt. 18.7.1991, w.e.f. 17.8.1991.
2. Subs by GSR 466, dt. 18.7.1991, w.e.f. 17.8.1991.
3. Subs by GSR 466, dt. 18.7.1991, w.e.f. 17.8.1991.
4. Added by GSR 45, dt. 1.1.1993, w.e.f. 23.1.1993
5. Subs. by GSR 45, dt. 1.1.1993, w.e.f. 23.1.1993.
6. Subs. by GSR 466, dt. 18.7.1991, w.e.f. 17.8.1991.
7. Added by GSR 466, dt. 18.7.1991, w.e.f. 17.8.1991.
8. Ins. by GSR 45, dt. 1.1.1993, w.e.f. 23.1.1993.
9.. Ins. by GSR 466, dt. 18.7.1991, w.e.f. 17.8.1991.
10. Subs. by GSR 253, dt. 19.2.1981, w.e.f. 7.4.1981.
11. Ins. by GSR 466, dt. 18.7.1991, w.e.f. 17.8.1991
127. Shot-firing-
(1) When shot-firing is in progress adequate precautions shall be taken to
protect apparatus and conductors other than those used for shot-firing from
injury.
(2) Current from lighting or power circuits shall not be used for firing shots.
(3) The provisions of rule 123 shall apply in regard to the covering and
protection of shot-firing cables, and adequate precautions shall be taken to
prevent such cable touching other cables and apparatus.
128. Signalling- Where electrical signalling is used-
(a) Adequate precautions shall be taken to prevent signal and telephone
wires coming into contact with other cables and apparatus;
(b) The voltage used in any one circuit shall not exceed 30 volts; and
(c) Contact-makers shall be so constructed as to prevent the accident closing
of the circuit.
1[(d) Bare conductors, where used shall be installed in suitable insulators.]
1. Ins. by GSR 45, dt. 1.1.1993, w.e.f. 23.1.1993.
129. Haulage- Haulage by electric locomotives on the overhead trolley-wire
system, at medium or low voltage, and haulage by storage battery locomotives
may be used with the prior consent in writing of the Inspector, and subject to
such conditions as he may impose in the interests of safety
130. Earthing of neutral points- Where the voltage of an alternating current
system exceeds 30 volts, the neutral or mid-point shall be earthed by connection
to an earthing system in the manner prescribed in rule 115.
Provided that when the system concerned is required for blasting and signalling
purposes, the provisions of this rule shall not apply.
1[Provided further that in case of unearthed neutral system adequate protection
shall be provided with the approval of the Inspector.]
1. Ins. by GSR 45, dt. 1.1.1993, w.e.f. 23.1.1993.
1[131. Supervision-
1. Subs by GSR 253, dt. 19.2.1983, w.e.f. 7.3.1983.
(1) (i) One or more electrical supervisors as directed by the Inspector
shall be appointed in writing by the owner, agent or manager of a mine or by the
agent or the owner, of one or more wells in an oil field to supervise the
installation.
(ii) The electrical supervisor so appointed shall be the person holding a valid
Electrical Supervisor’s Certificate of Competency, covering mining installation
issued under sub-rule (1) of rule 45.
(iii) If the Inspector considers necessary for the compliance with the duties
specified in this rule, he may direct the owner or agent of the mine to appoint one
or more electricians who shall be persons holding licence under sub-rule (1) of
rule 45.
(2) Every person appointed to operate, supervise, examine or adjust any
apparatus shall be competent to undertake the work which he is required to
carryout as directed by the engineer.
(3) The electrical supervisor shall be responsible for the proper performance
of the following duties, by himself or by electrician appointed under sub-rule (1):-
(a) Through examination of all apparatus (including the testing of earth
conductors and metallic coverings for continuity) as often as may be necessary
to prevent danger;
(b) Examination and testing of all new apparatus, and of all apparatus, re-
erected in the mine before it is put into service in a new position.
(4) In the absence of any electrical supervisor for more than three days, the
owner, agent or manager of the mine or the agent or owner of one or more oil-
wells in an oil-field, shall appoint in writing a substitute electrical supervisor.
(5) (i) The electrical supervisor or the substitute electrical supervisor
appointed under sub-rule (4) to replace him shall be personally responsible for
the maintenance at the mine or oil-field, of a long book made up of the daily log
sheets prepared in the form set out in Annexure-XII.
(ii) The results of all tests carried out in accordance with the provisions of
sub-rule (3) shall be recorded in the log-sheets prepared in the form set out in
Annexure-XII.]
132. Exemptions- The provisions of rules 110 to 128 both inclusive and rule
131 shall not apply in any case, where, on grounds of emergency or special
circumstances, exemption is obtained from the Inspector. In granting any such
exemption the Inspector may prescribe such conditions as he thinks fit.
CHAPTER XI
MISCELLANEOUS
133. Relaxation by Government-
(1) The State Government, or where mine, oil-fields or railways or works
executed for or on behalf of the Central Government, are affected, the Central
Government, may by order in writing, direct that any of the provisions of rules in
Chapter IV other than rules 44A and 46, and all rules in Chapters V, VI, VII, VIII
and IX shall be relaxed generally or in particular case to such extent and subject
to such conditions as it may think fit.
(2) The Central Government may, by order in writing, direct that any of the
provisions of Chapter X of these rules shall be relaxed in any particular case to
such an extent and subject to such conditions as it may think fit.
134. Relaxation by Inspector- The Inspector, may, by order in writing, direct
that any of the provisions of rules 44, 1[50 (1)(a), (b) and (d), 50 A (2), 51 (1)], 61
(2), 63, 64(2), 65,71 to 73 (inclusive), 76 to 80 (inclusive), go, 2[118], 119(l)(a),
123(5), 123(17), 2[123(9) and 130], shall be relaxed in any case to such extent
and subject to suit conditions as he may think fit.
(2) Where the voltage of any system does not exceed 125 volts the Inspector
may, by order in writing, direct that any of the provisions of rules 29 to 34
(inclusive), 36 to 39 (inclusive), 83, 92, 94 to 107 (inclusive) shall, in addition to
the rules specified in Sub-rule (1), be relaxed as regards such systems to such
extent and subject to such conditions as he may think fit.
(3) Every relaxation so directed shall be reported forthwith to, and shall be
subject to disallowance or revision by, the State Government, or where the
relaxation affects mines, oil-fields or railways, by the Central Government.
1. Subs by GSR 45, dt. 1.1.1993, w.e.f. 23.1.1993.
2. Subs by GSR 466, dt. 18.7.1991, w.e.f. 17.8.1991.
135. Supply and use of energy by non-licensees and others- Where any person
other than a non-licensee is supplied with energy by a non-licensee or other
person or has his premises for the time being connected to the conductors or
plant of a non-licensee or other person, or himself generates energy and uses
such energy or part thereof, such person shall be deemed to be a consumer for
the purposes of rules 9, 10, 29 to 33 (inclusive), 45 to 70 (inclusive), 87 and 142
and non-licensee or other person shall be subject to all the liabilities imposed on
a licensee by these rules.
136. Responsibility of Agents and Managers- Where any person is responsible
for the observance of any of these rules, every agent and manager of such
person shall also be responsible for such observance in respect of matters under
their respective controls.
137. Mode of entry- All persons entering in pursuance of the Act or these rules,
any building which is used as a human dwelling or a place of worship shall, in
making such entry have due regard so far as may be compatible with the
exigencies of the purpose for which such entry is made, to the social and
religious usages or the occupant of the building entered.
138. Penalty for breaking seal- Where, in contravention of rule 56 any seal
referred to in that rule is broken-
(a) The person breaking the seal shall be punishable with fine which may
extend to two hundred rupees; and
(b) The consumer when he has not himself broken the seal shall be
punishable with fine which may extend to fifty rupees unless he proves that he
used all reasonable means in his power to ensure that the seal should not be
broken.
1[138A. Penality for breach of rule 44A- Where, in contravention of rule 44A, any
person responsible for the generation, transformation, transmission, conversion,
distribution, supply or use of energy fails to report to the Inspector and other
authorities concerned the occurrence of accidents, such person shall be
punishable with fine which may extend to three hundred rupees.
1. Ins. by GSR 523, dt. 28.3.1966, w.e.f. 9.4.1966.
139. Penalty for breach of rule 45- Where any electrical installation work of the
nature specified in sub-rule (1) of rule 45 has been carried out otherwise than--
(a) Under the direct supervision of a person holding a certificate of
competency issued by the State Government under that rules; and
(b) In the absence of any applicable exemption under the proviso to sub-rule
of that rule, by an electrical contractor licensed by the State Government in this
behalf,
The consumer owner or occupier, the contractor (if any) or the person through
whom the work is being or was carried out and the person under whose
immediate supervision the work is being or was carried out, shall each be
punishable with fine which may extend to three hundred rupees.
1[140. Penalty for breach of rule 82-
(a) Where no notice is given under rule 82(l) or the amount of estimate as
demanded under rule 82(2) is not deposited, both the persons proposing and the
contractor engaged for erecting a new building or structure whether permanent or
temporary or for making in or upon an building or structure any permanent or
temporary additions or alterations, shall be deemed to have committed a breach
of rule 82(l) and shall be punishable with a fine which may extend to three
hundred rupees.
(b) If any person commences or continues any work in contravention of rule
82(3), in or upon any such building, structure, flood bank, road or carries out
addition or alteration thereto, the person contravening the same shall be
punishable with a fine which may extend to three hundred rupees.
In addition to this the supplier shall, after obtaining the concurrence of the
Inspector discontinue the supply, if any, to such building, structure, flood bank, or
road etc. but only after giving forty-eight hours notice to the person concerned in
writing of disconnection of supply and shall not commence the supply until he
and the inspector are satisfied that the cause has been removed.]
1. Subs by GSR 529, dt. 11.7.1986, w.e.f. 19.7.1986.
1[140A. Penalty for breach of rule 77,79 or 80- Where a person is responsible for
any construction which is or which results in contravention of the provisions of
rule 77, 79 or 80 he and the contractor whom he employs shall be punishable
with a fine which may extend to three hundred rupees, and in the case of
continuing breach, with a further daily fine which may extend to fifty rupees.
1. Ins. by GSR 1723, dt. 21.11.1977, w.e.f. 31.12.1977.
141. Penalty for breach of rules- Any person other than an Inspector or any
officer appointed to assist the Inspector who being responsible for the
observance of any of these rules commits a breach thereof, shall be punishable
for every such breach with fine which may extend to three hundred rupees, and
in the case of a continuing breach with a further fine which may extend to fifty
rupees, for every day after first during which the breach has continued.
142. Application of rules- Subject to the provisions of sub-section (2) of section
58, these rules shall be binding on all persons, companies and undertakings to
whom licences have been granted or with whom agreements have been made by
or with the sanction of Government for the supply or use of electricity before the
commencement of the Act.
143. Repeal- The Indian Electricity Rules, 1937, are hereby repealed.
Provided that any order made, notification issued or anything done or any action
taken under any of the said rules shall be deemed to have been made, issued,
done or taken under the corresponding provisions of the rules.