Form 28, Uttar Pradesh Factory Rules, 1950: 36[FORM 28
Uttar Pradesh Factory Rules, 1950 - Form 28
Text of form 28
36[FORM 28
36[FORM 28
[Prescribed under Para 7(2) of Schedule V to Rule 109] Report of Examination
and Test of Dust Extraction of Supersession System
1. Description of system
2. Hood-
(a) Serial number of hood
(b) Contaminant captured
(c) Capture Velocities (at points to be specified)
Design Value Actual Value
(d) Volume exhausted at hood
(e) Hood Static Pressure
3. Total Pressure drop at-
(a) Joints
(b) Other points of system (to be specified)
4. Transport velocity in duct at points along ducts (to be specified)
5. Air cleaning device-
(a) Type used
(b) Velocity at inlet
(c) Static pressure at inlet
(d) Velocity at outlet
(e) Static Pressure at outlet
6. Fan-
(a) Type used
(b) Volume handled
(c) Static Pressure
(d) Pressure drop at outlet of fan
7. Fan Motor-
(a) Type
(b) Speed and power in kilowatts
36
Ins. by Noti. No. 501/XXXVI-3-2(f)-85, dt. 14.5.1992.
8. Particulars of defects, if any, disclosed during test of any of the above
components.
I CERTIFY that on (date ......) the above dust extraction system was thoroughly
cleaned and (so far as its construction permits) made available for thorough
examination. I further certify that on the said date, I thoroughly examined the
above dust extraction system including its components and fittings and that the
above is a true report of my examination.
Signature
Qualification
Address
Date
If employed by a company or association, name and address of the
company or association.]
-----------