Regulation 113, Indian Boiler Regulations, 1950: Flat End Plates
Indian Boiler Regulations, 1950 - Regulation 113
Text of regulation 113
Flat End Plates
113. Flat End Plates.—(a) The end plates of boilers shall preferably be in one
piece made from one rolled plate. Alternatively, the end plates shall be built up
by butt-welding two pieces. In the latter case the line of welding shall be parallel
to the horizontal axis of the boiler and shall run through the centre line of furnace or
furnaces of Lancashire boilers and between two rown of stays of marine type boilers.
In tho ease of flat end plates the fusion welding, shall comply with stress relieving
(requirements and in the ease of dished end plates the fusion welding shall be aub-
jeotcd to both stress relieving and radiographio examination.
(b) The peripheral flanging of end plates shall be done by machine. Such
flanging shall preferably be dono in ono operation, but whore this is impracticable
sectional or creep machine flanging may be permitted, pro\ ided that the plate in
worked at a suitable temperature, and the plate is heated to an adequate distance
beyond the portion under immediate treatment.
(c) Care must be taken to see that the flanges arc circular and of good surface,
free from local irregularities, and that they are parallel a ad square with the flat
part of the plate. For the purpose of relieving internal stresses, all plates which
have been Hanged or locally heated shall afterwards be efficiently annealed unless
during the laat utage of manufacture they have been uniformly heated through-
out.
(d) Flat portions of end plates, on completion of all flanging and machining
operations, shall be flat and free from set or distortion.