211. Minimum thickness and cross section.—To provide a secure attachment
for plain tubes in the tube plates the thickness .xud cross section, of tho plate between
the tube holes shall not be less than • —
Steei tube plate,
•125D+ -2—minimum thickness in inches . . . . Eqn. (47)
•17D+ 025 ̂ minimum cross section in square inches . . Eqn. (48)
Copper tube plate,
• 2D+-4—minimum thickness in inches Eqn. (49)
•527D— -203=minimum cross section in square inohes . . Eqn. (50)
D is the diameter in inches of the tube at tho part of attachment to tubo plate.
Where the thickness and cross section of the tubo plates are less than the minimum
the appropriate co-efficient jn Eqn. (51) shall bo reduced in proportion to the
deficit.