Solid screwed stays

202. Solid screwed stays.—For sorew stays to oombustion chambers and fire boxes and for longitudinal and cross stays, the maximum working pressure for the stays is to be calculated from the appropriate one of tho following two formulae :— C / 1•28 \ " W.P. = — ( D I Kqn. (S») A \ N / CxIV W.P. = - - — Eqn (40) A W P. is the working pressure in lbs. per square inch, D is the diameter of stays over tljreads in inches, Da is the diameter of body of stay at its smallest part in inchest, N is the number of threads of stay per inch, A is the area in square inches supported by one stay [for area to be Hupported by stays near tubes in firebox tube plates of loootype boilers, see Regulation 193(0)], 0=7100 for steel or special wrought iron screw stays to combustion chamber or fireboxes C=8640 for stool longitudinal or cross stays fitted with nuts, C=4700 for i-oppor screw stays to fireboxes. Where stays are made with enlarged ends and the body of the stay IH smaller in diameter than at the bottom of the thread the working pressuro shall be calculated from tho second formula.