Regulation 114, Indian Boiler Regulations, 1950.: Strengthening of Flat End Plate at Manhole

Indian Boiler Regulations, 1950. - Regulation 114

Text of regulation 114

Strengthening of Flat End Plate at Manhole

114. Strengthening of Flat End Plate at Manhole.—(a) In the End Plates of Lancashire Boiler type the raudhole in the lower part of the front end plate shall be fitted with a flanged rivetod strengthening ring, the thickness of the flat portion of which shall be not less than (1-5 T X1/8 in.) where T equals the thickness of the end plate in inches. (b) In boilers 7 ft. 6 in. diameter and above, the mudhole frame shall be fitted "with a peak to reinforce the portion of tho end plate between and below the furnaoeB, and this peak shall be .securely riveted thereto with rivets of similar pitch to the remainder of the frame. (c) In all cases the front end plate gussot stays below tho furnaoes shall be placod a,s closely as possible to tho mudhole frame. (d) Where flat end plates are flanged for connection to the shell, the inside Tadius of flanging shall bo not. less than ) -75 times the plate thickness, with a minimum of 1 | m.