35. Tubes—(a) Process.—The copper shall bt fire-rofined or olootrolytio and
shall bo made into tubes eithei by tho hot rolling or cold drawing piocess. The
tubes shall be finished by cold drawing.
(b) Chemical Composition.—To comply with Regulation 33(b).
(c) Freedom from Detects.—The finished 1ubof», both externally and internally
shall be sound, clean, smooth well finished and free from surface defects and longi-
tudinal grooving, and the ends must bo clean and square.
(d) Tolerance.—Tho actual weight of oaoh tube ahall not be more than 6%
above the calculated weight. Unions, otherwise specified, they shall be straight
cylindrical, of uniform tki<knoas and external diameter throughout.
(e) Treatment o! Test Specimens.—All teat material, if not already hi an annealed
condition, shall be annealed before testing and shall comply with the mechanical
tests without further heat or mechanical treatment.
16 X. _U GAZETTE OP INDIA EXTRAORDINARY [PABT II
OOLD DRAWN SEAMLESS STEEL BOILER AND SUPERHEATER TUBES—
FOR DESIGNED STEAM TEMPERATURE NOT EXCEEDING
850°F (454°0)