Regulation 134, Central Electricity Authority (Measures relating to Safety and Electric Supply) Regulations, 2023: General safety requirements

Central Electricity Authority (Measures relating to Safety and Electric Supply) Regulations, 2023 - Regulation 134

Text of regulation 134

General safety requirements

134. General safety requirements. – (1) A separate emergency source of illumination with automatic initiation shall be provided in every room or campartment of gas insulated substation. (2) Cable cover protection unit shall be provided between flanges of gas insulated substation and cable termination unit. (3) Gas insulated substation installation of 220 kV and above voltage shall be provided with partial discharge monitoring system. (4) SF6 gas leakage rate from any single compartment of gas insulated substation to atmosphere and between compartments shall not exceed as stipulated in the relevant standards.