Regulation 134, Central Electricity Authority (Measures relating to Safety and Electric Supply) Regulations, 2023: General safety requirements
Central Electricity Authority (Measures relating to Safety and Electric Supply) Regulations, 2023 - Regulation 134
Text of regulation 134
General safety requirements
134. General safety requirements. – (1) A separate emergency source of illumination with automatic initiation shall
be provided in every room or campartment of gas insulated substation.
(2) Cable cover protection unit shall be provided between flanges of gas insulated substation and cable
termination unit.
(3) Gas insulated substation installation of 220 kV and above voltage shall be provided with partial
discharge monitoring system.
(4) SF6 gas leakage rate from any single compartment of gas insulated substation to atmosphere and between
compartments shall not exceed as stipulated in the relevant standards.