Regulation 109, Central Electricity Authority (Measures relating to Safety and Electric Supply) Regulations, 2023: Flexible cables
Central Electricity Authority (Measures relating to Safety and Electric Supply) Regulations, 2023 - Regulation 109
Text of regulation 109
Flexible cables
109. Flexible cables. – (1) Flexible cables for portable or transportable apparatus shall be two core or multi core,
unless required for electric welding, and shall be covered with insulating material which shall be efficiently
protected from mechanical injury.
(2) If flexible metallic covering is used either as the outer conductor of a concentric cable or as a means of
protection from mechanical injury, it shall not be used by itself to form an earth conductor for such apparatus,
but it may be used for that purpose in conjunction with an earthing core.
(3) Every flexible cable intended for use with portable or transportable apparatus shall be connected to the
system and to such apparatus by properly constructed connectors:
Provided that for machines of voltage exceeding 650 V but not exceeding 11 kV a bolted type connector
shall be used and the trailing cable shall be suitably anchored at the machine end.
(4) At every point where flexible cables are joined to main cables, a circuit breaker shall be provided which is
capable of automatically disconnecting the supply from such flexible cables.
(5) Every flexible cable attached to a portable or transportable machine shall be examined periodically by the
person designated to operate the machine, and if such cable is used underground, it shall be examined at least
once in each shift by such person and if such cable is found to be damaged or defective, it shall forthwith be
replaced by a cable in good condition.
(6) If the voltage of the circuit exceeds 250 V, all flexible cables attached to any transportable apparatus shall
be provided with flexible metallic screening or pliable armouring and cables of portable apparatus shall be
provided with flexible metallic screening on all the power and pilot cores:
Provided that the provision of this regulation shall not apply to flexible cables attached to any
transportable or portable apparatus used in open cast mines or below ground mines where reeling and unreeling
of such cables is necessary as per design features of the equipment.
(7) All flexible metallic screening or armouring specified in sub-regulation (6) shall fulfill the requirement
specified in clause (iv) of regulation 108:
Provided that in the case of separately screened flexible cables the conductance of each such screen
shall not be less than twenty five per cent of that of the power conductor and the combined conductance of all
such screens shall in no case be less than that of 0.15 sq. cm copper conductor.
(8) Flexible cable exceeding hundred metre in length shall not be used with any portable or transportable
apparatus:
Provided that such flexible cable when used with coal cutting machines or cutter or loader or armoured
face conveyor for long wall operation, or with shuttle cars or load haul dumper or cutter loader or all alike
equipment for development and de-pillaring operation shall not exceed two hundred fifty metre in length:
Provided further that the aforesaid cable in case of an open cast mine when used with electrically
operated heavy earth moving machinery shall not exceed six hundred metre in length and for bucked wheel
excavator at 11 kV shall not exceed one thousand metre in length:
Provided also that in case of dragline or 42 cubic metre capacity shovel, flexible cable length may be
raised up to 600 metre.
(9) Flexible cable, when installed in a mine, shall be efficiently supported and protected from mechanical
injury.
[भाग III—खण्ड 4] भारतकाराजपत्र:असाधारण 139
(10) Flexible cables shall not be used with apparatus other than portable or transportable apparatus:
Provided that, in case of applications like, submersible pumps, and skid mounted pumps, installed in the
mines, the use of flexible cable is allowed subject to the follow of measures as to prevent the mechanical damage
to the cables.
(11) Where flexible cables are used they shall be detached or otherwise isolated from the source of supply when
not in use, and arrangements shall be made to prevent the energising of such cables by undesignated persons.