Regulation 79, Central Electricity Authority (Measures relating to Safety and Electric Supply) Regulations, 2023: Laying of cables
Central Electricity Authority (Measures relating to Safety and Electric Supply) Regulations, 2023 - Regulation 79
Text of regulation 79
Laying of cables
79. Laying of cables. – (1) No underground power cable of voltage level up to 33 kV shall be laid without a
minimum underground depth from ground surface to top of the cable as per relevant standards:
Provided that the underground power cable meant for use exceeding 33 kV shall be laid with a minimum
underground depth of 1.2 metre.
(2) No underground telecommunication cable shall be laid without a minimum separation distance of 0.3 metre
132 THE GAZETTE OF INDIA : EXTRAORDINARY [PART III—SEC.4]
and 0.6 metre to the underground power cable of voltage up to 33 kV and exceeding 33 kV, respectively.