LawGrids logoLAWGRIDS.ORG

Regulation 44, Central Electricity Authority (Measures relating to Safety and Electric Supply) Regulations, 2023: Residual Current Device

Central Electricity Authority (Measures relating to Safety and Electric Supply) Regulations, 2023 - Regulation 44

Text of regulation 44

Residual Current Device

44. Residual Current Device. – The use of electricity to electrical installation, shall be controlled by a residual current device to disconnect the supply having rated residual current and duration as per the relevant standards: Provided that in domestic installation, residual current device having residual operating current not 116 THE GAZETTE OF INDIA : EXTRAORDINARY [PART III—SEC.4] exceeding 30 milliampere shall be used: Provided further that such protective device shall not be required for supply lines having protective devices which are effectively bonded to the neutral of supply transformers and conforming to regulation 76. Chapter VI Safety provisions for electrical installations and apparatus of voltage exceeding 650 V

Previous and next

All provisions of Central Electricity Authority (Measures relating to Safety and Electric Supply) Regulations, 2023

Questions people ask

Is regulation 44 of Central Electricity Authority (Measures relating to Safety and Electric Supply) Regulations, 2023 still in force?

No repeal of Central Electricity Authority (Measures relating to Safety and Electric Supply) Regulations, 2023 is recorded.