Rule 10, The Ammonium Nitrate Rules, 2012: Recovery of Spillage during handiing
The Ammonium Nitrate Rules, 2012 - Rule 10
Text of rule 10
Recovery of Spillage during handiing
10. Recovery of Spillage during handiing.——- If any spillage occurs
during the process of handling of Ammonium Nitrate at any stage,
2545 Gl/2012—13
98 THE GAZETTE OF INDIA : EXTRAORDINARY [PART li——SEC. 3(1)}
it should be carefully collected and bagged and accounted for and
the spillage, if not contaminated, may be transferred expeditiously
only to a licensee after proper accounting.
1.1. Speeiai precautions against accident."—
(1) No person shall commit or attempt to commit any act which
may tend to cause a fire or explosion in or about any place
where the Ammonium Nitrate is manufactured, converted,
bagged, stored or transported.
(2) Every person possessing Ammonium Nitrate and every person
in charge of or engaged in the import, export, manufacture,
conversion, bagging, sale, transport or handling of the
Ammonium Nitrate shall at all times comply with the
provisions of these Ruies and the conditions of the licence
relating thereto and observe all due precautions for the
prevention of thefts or accidents by fire or explosion.
(3) The premises used for storage of the Ammonium Nitrate shall
not be used for storage of' any other materials including
fertilizers. ‘
(4) Every person Shall prevent any other person from committing
any such act as is prohibited under sub—rule (1)
12?; Restrietien 1111 unauthorised persons, provision of guards and
safety distance 1111' storehouse— \
{1) The licence holder shall at his own expense provide security
guards for safe custody of Ammonium Nitrate stored in a
storeh ouse.
(2) For the purposes of sub—rule (1), the security guards shall be of
such strength as the District Authority may consider it to be
sufficient.
(3) The premises used for manufacture of the Ammonium Nitrate or
conversion of the melt into solid form of Ammonium Nitrate or
Vice versa and the storehouse shall be surrounded by a wall of at
[111:1 1h Eve 3(1)] 111111 61111161111 13111111101 ()9
least two metres height of such strength and construction as to
effectively prevent entry of unauthorised persons. 1.
(4) (a) The Ammionium Nitrate storehouse shall maintain;
(i) for storage not exceeding 30 MT Safety Distance of 4.5
metres from st01e housse to the compound wall and 45
metres frotm any protected works;
(ii) for st01age exceeding 30 MT, Safety Distance of 9 metres
from storehouse to the compound wall and 90 metres from
any protected works; '
(b) the storehouse may be adjacent to the baggingunit of the
manufacturing, conversion 01 explosives or nitrous oxide
manufacturing plants, but shall observe the provisions of
clauses (i) and (ii) of sub—rule (a) of rule 4.
Note: The safety distance shall be measured from the edge
ofthe torehouse.
(5) (a) The storehofuse shall be;
(i) construf ted at ground level without any mezzanine floor,
upper 111101 or any basement; I
(ii) with thh floor(plinth) level not less than forty five
centimetgres from the ground level and well ventilated;
(iii) with a1 least 23 centimetres thick walls built of brick or
stone ntortar, or concrete and with roof of RCC or
AsbestQ/s or Fibre or G1 sheet;
(iv) with/‘Vsuffieient numbers of doors made of steel of
minij/um three millimetres thick and opening outwards;
(b) Notwitk standing anything contained in subclause (iii)
storehouse f stevedore may be a shed without side walls.
(6) Any storehause used for possession for sale or possession for use
of Ammonium Nitrate shall have a floor area not less than one
square metre per Metric Tonne of Ammonium Nitrate and the
100 THE GAZETTE OF INDIA EXTRAORDINARY _ [PARI I]———SEC. 30)]
stOIehouse total holding capacity shall not exceed 5000 MT
storage: ,
Provided that one stack of bagged Ammonium Nitrate shall
not exceed 200 MT and a minimum clearance of two metres
shall be maintained between the adjacent stacks and at least 0.6
metre wide gangway shall be maintained between the stacks and
the walls 0f the storehouse
Provided further that the maximum staekyheight shall not
exceed 2.5metres from the floor level and the same shall be
prominently marked on the walls of the storehoUse
(7) The storehouse shall be protected against lightning as per IS
2309
(8) The storage tank meant for storage of Ammonium Nitrate melt
shall be —
(i) constructed of stainless steel or any other compatible
material according to sound engineering praetice conforming
to a national or international code accept d by the Chief
Controller and adequately insulated and suEported so as to
ensure safety and stability during loading a d unloading of
Ammonium Nitrate melt into or from such st rage tank;
(ii) with a secondary containment in the form 0 dyke enclosure
made of cement concrete and its holding cap‘ city shall not be
less than the capacity of the largest tank situited within such
enclosure; 1
(iii)observing Safety Distance of 4. 5 memes within the
compound wall and plant facilities and 45 n1etres from any
protectedworks;1
(iv) with single storage tank capacity not exceedingNZOOMT; and
(V) provided with a suitable hard stand adjacent to t for loading
and unloading and such a hard stand shall be located so that
its centre maintains a minimum safety distance of 4Smetres
all around. ‘
E3, Prohibition of certain acts -— No person shall _.__
1'
[um {Pave 3m] arm amW :amtw 101
(i) provide false or misleading information or declaration in any
application made or statement submitted under these rules; or
(ii) falsify, erase 0r fraudulently alter any entry in any log book,
document or other record required to be kept or maintained
under these rules; or
(iii)change or alter any licence, or other documents issued under
these rules.
Previous and next
Questions people ask
Is rule 10 of the Ammonium Nitrate Rules, 2012 still in force?
No repeal of the Ammonium Nitrate Rules, 2012 is recorded.