Rule 42, Atomic Energy (Factories) Rules, 1996: FIRE PROTECTION,PREVENTION & FIGHTING
Atomic Energy (Factories) Rules, 1996 - Rule 42
Text of rule 42
FIRE PROTECTION,PREVENTION & FIGHTING
42. FIRE PROTECTION,PREVENTION & FIGHTING.-
(1) Processes & equipment, plant, etc. involving serious explosion and serious fire hazards.-
(a) All processes, storages, equipments, plants etc. involving serious explosion and
flash fire hazard shall be located in segregated buildings where the equipment
shall be so arranged that only a minimum number of employees are exposed to
such hazards at any one time.
(b) All industrial processes involving serious fire hazard should be located in building
or work places separated from one another by walls of fire-resistant construction.
(c) Equipment and plant involving serious fire or flash fire hazard shall, wherever
possible, be so constructed and installed that in case of fire, they can be easily
isolated.
(d) Ventilation ducts, pneumatic conveyors and similar equipment involving a serious
fire risk should be provided with flame-arresting or automatic fire extinguishing
appliances or fire resisting dampers electrically interlocked with heat sensitive /
smoke detectors and the air-conditioning plant system.
(e) In all workplaces having serious fire or flash fire hazards, passages between
machines, installations or piles of material should be at least 90 cm wide. For
storage piles, the clearance between the ceiling and the top of piles shall not be
less than 2 m.
(2) Access for fire fighting. -
(a) Buildings and plants shall be so laid out and roads, passageways etc. so
maintained as
Atomic Energy Factory Rules, 1996
51
Rule 42
to permit unobstructed access for fire fighting. The main exit ways shall have
width not less than 4.5m. and vertical clearance not less than 5m.
(b) Doors and/or window openings shall be located in suitable position on all external
walls of the building to provide easy access to the entire area within the building
for fire fighting.
(3) Protection against lightning.- Protection from lightning shall be provided for-
(a) buildings in which explosive or highly flammable substances are manufactured,
used, handled or stored;
(b) storage tanks containing oils, paints, or other flammable liquids;
(c) grain elevators;
(d) buildings, tall chimneys or stacks where flammable gases, fumes, dust or lint are
likely to be present; and
(e) sub-station buildings and outdoor transformers / switchyards.
(4) Explosives.-All explosives shall be handled, transported, stored and used in accordance
with the provisions in the Indian Explosives Act, 1884 (4 of 1884).
(5) Precautions against ignition.-Wherever there is danger of fire or explosion from
accumulation of flammable or explosive substances in air-
(a) all electrical apparatus shall either be excluded from the area of risk or they shall
be of such construction and so installed and maintained as to prevent the danger of
their being a source of ignition;
(b) effective measures shall be adopted for prevention of accumulation of static
charges to a dangerous extent;
(c) workers shall wear shoes without iron or steel nails or any other exposed ferrous
materials which is likely to cause sparks by friction;
(d) smoking, lighting or carrying of matches, lighters or smoking materials shall be
prohibited;
(e) transmission belts with iron fasteners shall not be used; and
Atomic Energy Factory Rules, 1996
52
Rule 42
(f) all other precautions, as are reasonably practicable, shall be taken to prevent
initiation of ignition from all other possible sources such as open flames, frictional
sparks, overheated surfaces of machinery or plant, chemical or physical- chemical
reaction and radiant heat.
(6) Spontaneous ignition.- Where materials are likely to induce spontaneous ignition, care
shall be taken to avoid formation of air pocket and to ensure adequate ventilation. The
materials susceptible to spontaneous ignition shall be stored in dry condition and shall be
in heaps of adequate capacity and separated by adequate passage. The materials
susceptible to ignition and stored in the open shall be at a distance not less than 10 m.
away from process/storage buildings.
(7) Cylinders containing compressed gas.- Cylinders containing compressed gas may only be
stored in open if they are protected against excessive variation of temperature, direct rays
of sun, or continuous dampness. Such cylinders shall never be stored near highly
flammable substances, furnaces or hot processes. The room where such cylinders are
stored shall have adequate ventilation.
(8) Storage of flammable liquids.-
(a) The quantity of flammable liquids in any work room shall be the minimum
required for the process or processes carried on in such room. Flammable liquids
shall be stored in suitable containers with close fitting covers:
Provided that not more than 30 litres of flammable liquids having a flash point of
23 degree C or less shall be kept or stored in any work room without licence as
specified in Sec.8 of the Petroleum Act of 1934.
(b) Flammable liquids shall be stored in closed containers as specified in the
Petroleum rules and in limited quantities in well ventilated rooms of fire resisting
construction which are isolated from the remaining of the building by fire walls
and self closing fire doors.
(c) Large quantities of such liquids shall be stored in containers constructed of iron or
steel as per relevant I.S. Codes. These containers shall be stored in isolated and
adequately ventilated building of fire resisting construction or in storage tanks,
preferably underground and at a distance from any building as required in the
Petroleum Rules, 1976.
(d) Effective steps shall be taken to prevent leakage of such liquids into basements,
sumps or drains and to confine any escaping liquid within safe limits.
Atomic Energy Factory Rules, 1996
53
Rule 42
(9) Accumulation of flammable dust, gas, fume or vapour in air or flammable waste material
on the floors.-
(a) Effective steps shall be taken for removal or prevention of the accumulation in the
air of flammable dust, gas, fume or vapour to an extent which is likely to be
dangerous.
(b) No waste material of a flammable nature shall be permitted to accumulate on the
floors and shall be removed at least once in a day or shift, and more often, when
possible. Such materials shall be placed in suitable metal containers with covers
wherever possible.
(10) Fire exits.-
(a) In this rule-
(i) "horizontal exit" means an arrangement which allows alternative egress
from a floor area to another floor at or near the same level in an adjoining
building or an adjoining part of the same building with adequate
separation; and
(ii) "travel distance" means the distance an occupant has to travel to reach an
exit.
(b) An exit may be a doorway, corridor, passageway to an external stairway or to a
verandah or to an internal stairway segregated from the rest of the building by fire
resisting walls which shall provide continuous and protected means of egress to
exterior of a building or to an exterior open space. An exit may also include a
horizontal exit leading to an adjoining building at the same level.
(c) Lifts, escalators and revolving doors shall not be considered as exits for the
purpose of this sub-rule.
(d) In every room of a factory exits sufficient to permit safe escape of the occupants
in case of fire or other emergency shall be provided which shall be free of any
obstruction.
(e) The exits shall be clearly visible and suitably illuminated with suitable
arrangement, whatever artificial lighting is to be adopted for this purpose, to
maintain the required illumination in case of failure of the normal source of
electric supply.
(f) The exits shall be marked in a language understood by the majority of the
workers.
(g) Iron rung ladders or spiral staircases shall not be used as exit staircases.
(h) Fire resisting doors or roller shutters shall be provided at appropriate places along
the escape routes to prevent
Atomic Energy Factory Rules, 1996
54
Rule 42
spread of fire and smoke, particularly at the entrance of lifts or stairs where funnel
or flue effect may be created inducing an upward spread of fire.
(i) All exits shall provide continuous means of egress to the exterior of a building or
to an exterior open space leading to a street.
(j) Exits shall be so located that the travel distance on the floor shall not exceed 30m.
(k) In case of those factories where high hazard materials are stored or used, the travel
distance to the exit shall not exceed 22.5 m and there shall be at least two ways of
escape from every room, however small, except toilet rooms, so located that the
points of access there to are out of or suitably shielded from areas of high hazard.
(l) Wherever more than one exit is required for any room space or floor, exits shall
be placed as remote from each other as possible and shall be arranged to provide
direct access in separate directions from any point in the area served.
(m) The unit of exit width used to measure capacity of any exit shall be 50 cm. A clear
width of 25 cm. shall be counted as an additional half unit. Clear width of less
than 25 cm. shall not be counted for exit width.
(n) Occupants per unit width shall be 50 for stairs and 75 for doors.
(o) For determining the exits required, the occupant load shall be reckoned on the
basis of actual number of occupants within any floor area or 10 sq.m per person,
whichever is more.
(p) There shall not be less than two exits serving every floor area above and below the
ground floor, and at least one of them shall be an internal enclosed stairway.
(q) For every building or structure used for storage only, and every section thereof
considered separately, shall have access to at least one exit so arranged and
located as to provide a suitable means of escape for any person employed therein,
and in any such room wherein more than 10 persons may be normally present, at
least two separate means of exit shall be available, as remote from each other as
practicable.
(r) Every storage area shall have access to at least one means of exit which can be
readily opened.
Atomic Energy Factory Rules, 1996
55
Rule 42
(s) Every exit doorway shall open into an enclosed stairway, a horizontal exit on a
corridor or passageway providing continuous and protected means of egress.
(t) No exit doorway shall be less than 100 cm in width. Doorways shall be not less
than 200 cm. in height.
(u) Exit doorways shall open outwards, that is, away from the room but shall not
obstruct the travel along any exit. No door when opened, shall reduce the required
width of stairway or landing to less than 90 cm. Over head or sliding doors shall
not be installed for this purpose.
(v) An exit door shall not open immediately upon a flight of stairs. A landing of at
least 1.5m X 1.5m in size shall be provided in the stairway at each doorway. The
level of landing shall be the same as that of the floor which it serves.
(w) The exit doorways shall be openable from the side which they serve without the
use of a key.
(x) Exit corridors and passageways shall be of a width not less than the aggregate
required width of exit doorways leading from there in the direction of travel to the
exterior.
(y) Where stairways discharge through corridors and passageways, the height of the
corridors and passageways shall not be less than 2.4 m.
(z) In the case of enclosed staircases, all windows therein falling within 3m of any
other opening in the building shall normally be protected by wired glass in steel
framework. In the case of open sided staircases, windows and door openings of
the building falling within 3m of the staircase shall normally be protected by
wired glass in steel framework and single fireproof door respectively.
(aa) A staircase shall not be arranged round a lift shaft unless the latter is totally
enclosed by a material having a fire-resistance rating not lower than that of the
type of construction of the former.
(bb) Hollow combustible construction shall not be permitted.
(cc) The minimum width of an internal staircase shall be 100 cm.
(dd) The minimum width of treads without nosing shall be 25 cm. for an internal
staircase. The treads shall be constructed and maintained in a manner to prevent
slipping.
Atomic Energy Factory Rules, 1996
56
Rule 42
(ee) The maximum height of a riser shall be 19 cm. and the number of risers shall be
limited to 12 per flight.
(ff) Hand rails shall be provided with a minimum height of 100 cm. and shall be
firmly supported.
(gg) The use of spiral stair case shall be limited to low occupant load and to a building
of height of 9 m , unless they are connected to platforms such as balconies and
terraces to allow escapees to pause. A spiral staircase shall be not less than 300
cm. in diameter and have adequate head room.
(hh) The width of a horizontal exit shall be same as for the exit doorways.
(ii) The horizontal exit shall be equipped with at least one fire door of self closing
type.
(jj) The floor area on the opposite or refuge side of a horizontal exit shall be sufficient
to accommodate occupants of the floor areas served, allowing not less than 0.3
m2The refuge area shall be provided with exits adequate to meet the requirements
of this sub-rule. At lest one of the exits shall lead directly to the exterior or street.
(kk) Where there is difference in level between connected areas for horizontal exit,
ramps not more than 1 in 8 slope shall be provided. For this purpose steps shall
not be used.
(ll) Doors in horizontal exits shall be openable at all times.
(mm) Ramps with a slope of not more than 1 in 12 may be substituted for the
requirements of staircase. For all slopes exceeding 1 in 12 and wherever the use is
such as to involve danger of slipping, the ramp shall be surfaced with non-slipping
material.
(nn) In any building not provided with automatic fire alarm a manual fire alarm system
shall be provided if the total capacity of the building is over 500 persons, or if
more than 25 persons are employed above or below the ground floor, except that
no manual fire alarm shall be required in one-storey buildings where the entire
area is undivided and all parts thereof are clearly visible to all occupants.
(11) First-aid fire fighting arrangements.-
(a) In every factory there shall be provided and maintained adequate and suitable fire
fighting equipment for fighting fires in the early stages, those being referred to as
first-aid fire
Atomic Energy Factory Rules, 1996
57
Rule 42
fighting equipment in this rule.
b) The types of first-aid fire fighting equipment to be provided shall be determined
by considering the different types of fire risks which are classified as follows:-
(i) "Class A fire" - Fire due to combustible materials such as wood, textiles,
paper, rubbish and the like.
(1) "Light hazard" - Occupancies like offices, assembly halls ,
canteens, rest- rooms, ambulance rooms and the like;
(2) "Ordinary hazard" - Occupancies like saw mills, carpentry shop,
small timber yards, book binding shops, engineering workshop and
the like;
(3) "Extra hazard"-Occupancies like large timber yards, godowns
storing fibrous materials, flour mills, cotton mills, jute mills, large
wood working factories and the like;
(ii) "Class B fire" - Fire in flammable liquids like oil, petroleum products,
solvents, grease, paint, etc.
(iii) "Class C fire" - Fire arising out of gaseous substances.
(iv) "Class D fire" - Fire from reactive chemicals, active metals and the like.
(v) “Class E fire" - Fire involving electrical equipment and delicate machinery
and the like.
(c) The number and types of first-aid fire fighting equipment to be provided shall be
as given in Schedule I to this rule. For "ordinary hazard or extra hazard
occupancies equipments as given in sub-rule (12) shall be provided in addition to
that given in Schedule I.
(d) The first-aid fire fighting equipment shall conform to the relevant Indian
Standards.
(e) As far as possible the first-aid fire fighting equipment shall all be similar in shape
and appearance and shall have the same method of operation.
(f) All first-aid fire fighting equipment shall be placed in a conspicuous position and
shall be readily and easily accessible for immediate use. Generally, these
equipment shall be placed as near as possible to the exits or staircase landing or
normal routes of escape.
Atomic Energy Factory Rules, 1996
58
Rule 42
(g) All water buckets and bucket pump type extinguishers shall be filled with clean
water. All sand buckets shall be filled with clean, dry and fine sand.
(h) All other extinguishers shall be charged appropriately in accordance with the
instructions of the manufacturer.
(i) Each first-aid fire fighting equipment shall be allotted a serial number by which it
shall be referred to in the records. The following details shall be painted with
white paint on the body of each equipment.
(1) Serial number:
(2) Date of last refilling; and
(3) Date of last inspection.
(j) First-aid fire fighting equipment shall be placed on platforms or in cabinets or
hanged from brackets in such a way that their bottom is 750 mm above the floor
level. Fire buckets shall be placed on hooks attached to a suitable stand or wall in
such a way that their bottom is 750 mm above the floor level. Such equipment if
placed outside the building, shall be under shades or covers.
(k) All extinguishers shall be thoroughly cleaned and recharged immediately after
discharge. Sufficient refill material shall be kept readily available for this purpose
at all times.
(l) All first-aid fire fighting equipment shall be subjected to routine
maintenance, inspection, and testing to be carried out by properly trained
persons. Periodicity of the routine maintenance, inspection and test shall
conform to the relevant Indian Standards.
(12) Other fire fighting arrangements.-
(a) In every factory, adequate provision of water supply for fire fighting shall be made
and where the amount of water required in litres per minute, as calculated from
the formula A + B + C + D divided by 20 is 550 or more, power driven trailer
pumps of adequate capacity to meet the requirement of water as calculated above
shall be provided and maintained.
In the above formula -
A = the total area in sq.m of all floors including galleries in all buildings of the
factory;
B = the total area in sq.m of all floors and galleries including open spaces in
which combustible
Atomic Energy Factory Rules, 1996
59
Rule 42
material are handled or stored;
C = the total area in sq.m of all floors over 15 m above ground level; and
D = the total area in sq.m of all floors of all buildings other than those of fire
resisting construction:
Provided that in areas where the fire risk involved does not require use of water,
such areas under B,C or D may, for the purpose of calculation, be halved:
Provided further that where the areas under B, C or D are protected by permanent
automatic fire fighting installations approved by any fire association or fire
insurance company such areas may, for the purpose of calculation, be halved:
Provided also that where the factory is situated at not more than 3 km from an
established city or town fire service, the pumping capacity based on the amount of
water arrived at by the formula above may be reduced by 25%; but no account
shall be taken of this reduction in calculating water supply required under
clause(a).
(b) Each trailer pump shall be provided with equipment as per Schedule II to this rule.
Such equipment shall conform to the relevant Indian Standards.
(c) Trailer pumps shall be housed in a separate shed or sheds which shall be sited
close to a principal source of water supply in the vicinity of the main risks of the
factory.
(d) In factories where the area is such as cannot be reached by man-hauling of trailer
pumps within reasonable time vehicles with towing attachment shall be provided
at the scale of one for every four trailer pumps with a minimum of one such
vehicle kept available at all times.
(e) Water supply shall be provided to give flow of water as required under clause (a)
for at least 100 minutes. At least 50% of this water supply or 450,000 litres
whichever is less, shall be in the form of static tanks of adequate capacities (not
less than, 45,000 litres each) distributed round the factory with due regard to the
potential fire risks in the factory, where piped supply is provided the size of the
main shall not be less than 15 cm. diameter and it shall be capable of supplying a
minimum of 4500 litres per minute at a pressure of not less than 700 kPa
(7kg/sq.cm.)
(f) All trailer pumps including the equipment provided with them and the vehicles for
towing them shall be maintained in good condition and subjected to periodical
inspection and testing as
Atomic Energy Factory Rules, 1996
60
Rule 42
required.
(13) Personnel in charge of equipment and for fire fighting, fire drills, etc.-
(a) The first-aid and other fire fighting equipment to be provided as required in sub-
rules(11) and (12) shall be in charge of a trained responsible person.
(b) Sufficient number of persons shall be trained in the proper handling of fire
fighting equipment as referred to in clause (a) and their use against the types of
fire for which they are intended to ensure that adequate number of persons are
available for fire fighting both by means of first-aid fire fighting equipment and
others. Wherever vehicles with towing attachment are to be provided as required
in clause (d) of sub- rule (12) sufficient number of persons shall be trained in
driving these vehicles to ensure that trained persons are available for driving them
whenever the need arises.
(c) Fire fighting drills shall be held as often as necessary & at least once in every
period of two months.
(14) Adequate number of automatic sprinklers and fire hydrants shall be provided, in addition,
and not in substitution of the requirements in sub-rules (11) and (12).
(15) If the Competent Authority is satisfied in respect of any factory or any part of the factory
that owing to the exceptional circumstances such as inadequacy of water supply or
infrequency of the manufacturing process or for any other reason, to be recorded in
writing, all or any of the requirements of the rules are impracticable or not necessary for
the protection of workers, it may by order in writing (which it may at its discretion
revoke)exempt such factory or part of the factory from all or any of the provisions of the
rules subject to conditions as it may by such order prescribe.
Atomic Energy Factory Rules, 1996
61
Rule 42(Sch.I)
SCHEDULE I
First Aid Fire Fighting Equipments
1. The different type of fires and first aid fire fighting equipments suitable for use on them
are as under:
Class of Fire Suitable type of Appliances
A. Fires in ordinary combustibles (wood,
vegetable fibres, paper & the like)
Chemical Extinguishers of Soda-acid,
Gas/expelled Water and anti-freeze
types and water buckets.
B. Fires in flammable liquids, paints, grease,
solvents and the like
Chemical Extinguishers of foam, Carbon
dioxide and dry powder types and sand
buckets
C. Fires in gaseous substances under pressure Chemical Extinguishers of carbon
dioxide and dry powder types
D. Fires in Reactive Chemicals, active metals
and the like
Special type of dry powder extinguishers
and sand buckets
E. Fires in electrical equipments Chemical extinguishers of carbon
dioxide and dry Powder type & sand
buckets
2. One 9 litres water bucket shall be provided for every 100 sq.m. of the floor area or part
thereof and one 9 litres water type extinguisher shall be provided to six buckets or part
thereof with a minimum of one extinguisher and two buckets per compartment of the
building. Buckets may be dispensed with, provided supply of extinguishers is double that
indicated above.
3. Acceptable replacements for Water buckets and water type extinguishers in occupancies
where Class B fires are anticipated, are as under:
Atomic Energy Factory Rules, 1996
62
Rule 42 (Sch.I)
Buckets of water Water type
Extinguishers
Acceptable
Replacements
For one bucket For three buckets For each 9 ltrs.(or 2
gallons) Extinguishers
1 2-a 2-b 3
Dry sand 1 bucket 3 buckets -
Carbondioxide
Extinguishers
3 kg. (or 7 lbs) 9 kg. (or 20 lbs)
(In not less than 2
extinguishers)
9 kg.(or 20 lbs)
Dry powder 2 kg. (or 5 lbs) 5 kg. (or 11 lbs)
(In one or more
extinguishers)
5 kg. (or 11 lbs)
Foam extinguishers 9 litres(or 2 gallons) 9 litres (or 2 gallons) 9 litres (or 2 gallons)
4. The following provisions shall be complied with where Class E fires are anticipated:
(a) For rooms containing electrical transformers, switchgears, motors and/or other
electrical apparatus only, not less than two kg. Dry Powder or Carbon Dioxide
type extinguishers shall be provided within 15 m. of the apparatus.
(b) Where motors and/or other electrical equipment are installed in rooms other than
these containing such equipment only, one 5 kg. Dry Powder or Carbon Dioxide
Extinguisher shall be installed within 15 m. of such equipment in addition to the
requirements mentioned at (3) and (4) above. For this purpose the same
extinguisher may be deemed to afford protection to all apparatus within 15 m.
thereof.
(c) Where electrical meters are installed on platforms, one 2 kg. Dry Powder or
Carbon Dioxide type extinguisher shall be provided on or below each platform. In
case of a long platform with a number of motors, one extinguisher shall be
acceptable as adequate for every 3 motors on the common platform. The above
requirements will be in addition to the requirements mentioned at item (3) & (4)
above.
Atomic Energy Factory Rules, 1996
63
Rule 42 (Sch.I-II)
5. The first aid fire fighting equipments shall be so distributed over the entire floor area that
a person has to travel not more than 15 m. to reach the nearest equipment.
6. Selection of sites for the installation of first aid fire fighting equipments -
(a) While selecting sites for first aid fire fighting equipments, due consideration shall
be given to the nature of the risk to be covered. The equipments shall be placed in
conspicuous positions and shall be readily accessible for immediate use in all
parts of the occupancy. It should always be borne in mind while selecting sites
that first aid fire fighting equipments are intended only for use on incipient fires
and their values may be negligible if the fire is not extinguished or brought under
control in the early stages.
(b) Buckets and extinguishers shall be placed at convenient and easily accessible
locations either on hangers or on stands in such a way that their bottom is 750
mm. above the floor level.
7. The operating instructions of the extinguishers shall not be defaced or obliterated. In case
the operating instructions are obliterated or have become illegible due to passage of time,
fresh transfers of the same shall be obtained from the manufacturers of the equipments
and affixed to the extinguishers.
SCHEDULE II
EQUIPMENT TO BE PROVIDED WITH TRAILER PUMP
For light trailer pump of capacity of 680 ltrs./min.
Type of equipment Nos.
Armoured suction hose of 9 meters length, with wrenches. 1
Metal suction strainer. 1
Basket strainer. 1
Two-way suction collecting-head. 1
Suction adaptor. 1
Unlined or rubber lined 70 mm delivery hose of 25 meters length complete
with quick-release couplings.
10
Atomic Energy Factory Rules, 1996
64
Rule 42 (Sch.II)
Dividing breaching-piece. 1
Branch-piece with 15 mm nozzles. 2
Diffuser nozzle. 1
Standpipe with blank cap. 1
Hydrant key. 1
Collapsible canvas buckets. 4
Fire hook preventor with cutting edge. 1
25 mm manila rope of 30 meters length. 1
Extension ladder of 3 m (where necessary) 1
Heavy axe. 1
Spade. 1
Pick axe. 1
Crowbar. 1
Saw. 1
Hurricane lamp. 1
Electric torch. 1
Pair of rubber gloves. 1
For large trailer pump of a capacity of 1800 litres/minute
Type of equipment Nos.
Armoured suction hose of 9 meters length, with wrenches. 1
Metal strainer. 1
Basket strainer. 1
Three-way suction collecting-head. 1
Suction adaptor. 1
Unlined or rubber lined 70 mm delivery hose of
Atomic Energy Factory Rules, 1996
65
Rules 42(Sch.II)-43
25 meters length complete with quick-release couplings. 14
Dividing breaching-piece. 1
Collecting breaching-piece. 1
Branch pipes with one 25 mm, two 20 mm and one diffuser nozzles. 4
Stand pipe with blank caps. 2
Hydrant keys. 2
Collapsible canvas buckets 6
Coiling hook (preventor) with cutting edge. 1
50 mm manila rope of 30 meters length. 1
Extension ladder of 9 meters length (where necessary). 1
Heavy axe. 1
Spade. 1
Pick axe. 1
Crowbar. 1
Saw. 1
Hurricane lamp. 1
Electric torch. 1
Pair of rubber gloves. 1
Note:- If it appears to the Competent Authority that in any factory the provision of breathing
apparatus is necessary it may by order in writing require the occupier to provide suitable
breathing apparatus in addition to the equipment for light trailer pump or large trailer pump as
the case may be.