11.5 Technical Standards and Specifications including Safety Standards for City or Local Natural Gas Distribution Networks, Amendment Regulation, 2016
Regulations made under The Petroleum and Natural Gas Regulatory Board Act, 2006
This text is shown as one document.
Full text
TWH He Elo Teo -33004/99 REGD. NO. 1). L.-33004 99
Che Gazette of Gudia
EXTRAORDINARY
aeT 111—wave 4
PART Ifl—Section 4
Witter A wenrieTa
PUBLISHED BY AUTHORITY
a 426] a8 fecch, aewaftan, Aaa 24, 2016 /3TeTaTT 3, 1938
No. 426] NEW DELHI, THURSDAY. NOVEMBER 24, 2016/AGRAHAYANA 3, 1938
ateaarat
ae feet, 24 qatar, 2016
wa. waar Aavaristey1/2010.—taraas ae wafas ta fafrarre are afataaa, 2006 (2006 41
~ oS S
49) ft art 61 ert ves feet ar wae aera ev verre ate orpice ter Patras are wage werhaaa ay
opis try fates aré (aa ar cardia opie te Paco aca & fr are art ated aah are ae
fafarfeat), 2008 & astra aera & far faeries fateas sara Z, aaa:
1. Ty ots site I:
(1) va faa at tater aie sepia i fafsares are (ae at eatin aepite te eae aed Pere rer
ner aa vet are ae faferfot) astra fafare, 2016 Fer TT
(2) 3 fa Pore avatar Fora waren Hh are A aa ZT
2. dafere site separ ae fafa are Ce on earia oee ie a fare teak foro ara arta afer
aaa are ae fafsrfeat) fate 2008 4 -
(i) aPefore 1, aarhe seer 6 8, ofthe “weraqnt aes peta / afer," & spats "arin 9573 z1e7 IVF
aqey dia frente vag dre fan, frePafes, ohare Pear oo, art:
“areuy 9573 ZTE4 Il & aay Hara Feasts tae ST";
(i) afters 1 wate tear 9 8, ofthe “weeael saa | etre / ofa," a steals are fears oes “art
gfafer area, arvat waar arora aie fea arora ofearo "ae. are ara aprer oft arte,
sae are ae et", A ay rest & Pa, Poafafes a ofeat hte Pea ar, avast -—
ae
“arqraara wf Grat asa, array yates Ta ae Pafaea arrears wire) sare aera, ararepret Peper
ae, Prt aif ae Set a werd dere core St aor arraara ares Brad are Afar eras Te ZT,
S439 GE2016 ly
Nw
THE GAZETTE OF INDIA: EXTRAORDINARY [PART HII-—SEc. 4]
(iii)
(vi)
(vii)
(viii)
(ix)
(xi)
(xii)
(xiii)
ape F, fer ae aa sae A ae aaa area & far et ae Se” oft sa are eae ee "TS
4] Gla FT TAT STAT .... 7 AE esas ae ada va % fan aaa adi Zr A are reat Prater ar
“area St qreg / ela Soars H Hier a Ys Hat TATE He ee aT eT are",
aaa -# Hf, “carfeen oreu aie gee” ofthe aera are fewn nea * arts 14885 aT are oa aT 4437 .....
° aie. arerat 8085 att 3 aged He Peer eft gem” 4 vara sect at feafafed 4 ciertta
Pra arent, ATA:
“grec 14885 aT arse 4437 % ages oifafaaa(ss) qed sie arses 4437 apr 3 at Sus 1555 art
3% aqen We Pater eri en”:
ae &, “ores Fe: at i eater” ofthe santa ree oie are Ft aed aT At aa aT
enti’ ger fear sivas,
ata ar 4, “area az Feira arerrat Pafeer” oft tenia “areas 8085 aT 3% aed TAlcerfeea
fries aftart oni ax a Pafetea srasaarat ar go eat” sect at Prafafed a sfteeira fear som,
aTaat-
‘avast 4437 art 3 at gua 1555 am 3% aqed aatenites fee atari anit atx a fafataa
arora tT BT”:
aq, “area ate weifara & aera fee”, ofthe & sari so tara), sea “STA ae Beat FT Ga
aia Hh ae oT gai fear eT; aét Gist ar Se aa Bie Rafer
apt 1a 8, ais Aceh sare”, ware iv) va v) (ao Fo afaferr 241 A ee ae eri” seat FT
ear fear ae:
art 14 4, “orftes area ate aga feorea wef’, offer & aeela aries seq “corres cred AT Aare
Aaa Arete FTA oa “aie wm agar A aoa’, oe aaa seat aT frafetad 4 veri
fear sea, aT -—
aaa 1a F, “cafes Rafe ar fesse zara” ofits: & stenta “ast HS Fafa erga 8085 ant 3 aqaT
art arfew” seat a Frafetad & wheats fear are, area —
vat fre fates areca 4437 art 3 at iva 1555 at 3 aed Art aria’;
at 14, “cartes ey si aya & rs sar aaraera” ofthe F sashes, “Arar orazara” Hora Pafeer
#60 Haft. aie sae afae ares eg feed F aes wreeara erat alee” reat Bt ger fear soar:
apt 14 4, oo oft * sg zara eda, ardten aren, erat rer a carftem fae wore H te zara aT
For az dra” seat at Praferfee & ofeeertta Re arom, areaa:-
“sg cara eet ar SE face sort Fe zara ar fata aie aT”;
at 19 4, so ofits “weg cara Pron ore Fate cara an facta site tar” stata “eg cara far
yore 4 aea, wy arias ae og seit soa a te ase ae cifee cara ox St art 21" test Fr
ger fear area;
Lr Il—ave 4] and Fl ws: SI 3
(xiv)
(xvi)
(xvii)
(xviii)
(xix)
apr ta 8, ofthe, ary Far aed” oooftia: “Say area Al earear’ Srare Haat H arfere oe
“aft eres ores ate Prefer..." ate aa sare & Serrera soeea aero aA area" ses AT ae ae
Praferfaa er SST ST, ATA:
“pay Al Tees 375 Hat, oe er Ht Batt 2 aod fh ag Prafatae aravarrarat 1 WPS eect St
m. area zara 110 facta A afer ai ArT
. Wey ar eave 63 fit a afere ae em
T. arate dra vated fae afte (arch) era & are rea oe Se FH cat aT Aaa AT
oredr ara Ft aa at ae Sa ATA aT
4. Were aed oreo & Sat a 100 Aa. va et ai
eo ata arte ft ater spare 150 fat, arf
4. ctr ares a aria 82 4 arated fer aro
Saree Ft arareee site geates (Fqaren) Pear are wae Ft Tec HT 375 Ha. aH ee
aed & fora yaar 4 fafere aaa oe fer aro
ae ©. 8, safe “fare dadt ata & senta “are ot ar cosas Ft 31.8, ore on Ft afta
nam vestt at fate dat 8 adh serearitar & svar oe agar aT wae BI" ost aT Pefefee a
viteaite Pear sre area:-
“are ft ar craané af 31.8 F afta age veel at fare Sat HF at carafe H ares We aT aT
aaa aN";
ae 18. 8, cerfeen ged ar aye Ft aera” oo ofite & state “aera aeate Baer Ye Ara eae aT
ord At ft areata at ard fT CUTE FT 31.8 & ape eri arfeu” sect at afafea a cea
Fear sat, aa :-
“corftes Wey ay alfa $1 aeeaa Uae At 31.8% agar AAT are";
ada 14, SS. cre a eae BF are cree aa A Prat At aie ofite & saci so-ofrds, “area”
& fou arias oe “dior 9362.....° ae “aie area At PSPwar oe aaa ost aT Peafafea @
wfeeartte Pea sree, aaa —
“drug Sua arevaat 15761: tetferrs aie ofa te set 2a ie Ae, Taha Wa Se Tes, BTS ST
100 ax wie & farm”;
oda 14, SS. art a eps ea are cred ara At fafa At ach" ofa & ania soci, “area”
a fer acta seq “ATTA 5351 ........ ate... gre wate ate area” oe sare sect & foro Pefefas &
yfaearite aren, aaa:
“frra Sot aS Taat 17292 > Terferan, teria siz dae seit
aqda 1 4, nse. sr A seen gre arelt cred arf Ai Paforteeat At as” ofits & stent ea-ofnte
“fafera” F “arwer 1239 (amt 2) ete aga, acters ai area aga efie ft fee Peat an-1 were
aera aettare itz sora eer Ft af ter aren Pee” oreei at Pratafes & ofeearite som, area:
“SITET 1239 (aT1-2):38t4 Bla, Aiea sit ag etter Pelee. faforheat-are 2: ter oe Pafeer”:
THE GAZETTE OF INDIA : EXTRAORDINARY [PART HI—SEc. 4]
(xx)
(xxi)
(xxii)
(xxiii)
(xxiv)
(xxv)
(xxvi)
ayaa 1 8, Anse. 2 A ogee Sra art ren art Ft faferieat fr ast” oftte aw stenta otf,
‘caleem area” “iva 10204-a Por vate Pra area” seat at Prafefad @ ofeearhia fear aro,
aTat -—
“Em 10204 ard wee9 Sorat — Per searastt aT",
aaa 13, arf st. art 8 ee aa are aren art Ai Patera ft a oftere a stare softs, “treet
&t adt Pefen,” 3 orévs 319 frefen aes trea Ht we, AP ai ore ore — faforean:- " edt Fe TaTA
“Sua 12164: atat ae aan fara ara ae Belt wasras BE |
tua 12165: ara are arar Fafa ara Tet sie aa RT ets";
aq 24, fst st. zrat A setae erat area soeot Ft faforfeat At at ofa ae atte sosthrs.,"efat
(ara) Soa SETHUT AG / AATETHUA BIT31 STETA TT Alec” sreat et Prafatad a vfeartst
aan at 137-1 0a 2: ae teh”;
aga 24, sts. erat Fo eeaare Sa ara Soeur Ft faforteat Ft Sr” often stenta sro, ear
(arta) sree” F tos 1359 / Atos 4161 store Ae Hee” reat at fafa & ofrearftas Peat ao,
ATAT:-
“Area 1359: 1s est - eer ra dra";
ayaa 2 8, sftst. zat Ft eeaara aa area soeemt fr faferfeat fr ae ofttar steia satis,
“feet (ara) Sra” Fares a 32- AeA Pees Ta Hier aa zatea ta Her” seat at eet feat
amar,
ada 2 4, rst. erat Ho sere grt art soacot Ft faforfeat fr ae ofits & stata soretita
“STEUTA-12176-2: vatften wey ate fete — eysra saree oifererere
wore & Ferm Sea-ATT 2: See!
sual ara
“Eva 55014: faeqa arfera Arex aie gar ae et Soa Ie EST WATT Sq, Tea AT FAST
age sracn war feat faete faerearat At ara ae a Ae
eva 61000-6-3: fraaaratia svat (suet) . safer area-srarttr, arian ae gea-sirerAre
araTaeyt *& fare saat ATA
=u 61000-6-1 fagaaeatitr awaar (coat a1) SARs ATAT-STaTAT, arfirftan siz eep-sren Rr avarazor
array & Ferm Saree |
=74-61000-3-2: feraatte aaraar (Sua): APare- arate AT Ses (STE Saye AT < 160
aon) fr Arar
SF-60335-1: Fey AT AGA TEL STH: ATAT- ATT HATHA
EUA-60335-2-45; Aq AL AST TT STHLM: ATAT- Tear ATPST sits site ageT Tes STH | Fer
far araerrat";
ayes. IV 4, “ores cope ae afte areat yar Pru ag oftaré gredt ae ata Ft aya = few aaa
arse” ofthe 3 aenta soe “are At agin” F seat “ate Fr aye ar sites & fer soar At ar
art Petar aie dierent 1254 ant 1 ate 2 aes ev”, a eat feat aT
Cam W-are 4) Rd bl UTA: START wn
(xxvii) IV A, “ures soa ae atts area F carr Pew am sare creat ae ata Ft Byatt a
aac” otter & santa soothe “ara ft aqfa’ A “are arg dteainst 29453:1994 aaa ATE
AIST A-TATaS ASS Se SAH ST eT” seat ar fraPatad & ofrear ha Pear soa, ava:
“sare arg diva fue aiesst 9453: fea aertia aaa (fees): sais cesar, aia sie
areaT Tat, are
[fasrrry- 11/4/3787 ./3.16/2016]
ure fecquft : yea fafa ser ara ft. 612(a), feats 27 area, 2008 & veo afer ea ev ae aT ar. FF 750(a),
feaim 14.10.2009, haem wa(ars) F4ueay Asfigi/1/2010 fears 16.12.2014, mr. wa-faa/vi/i/2007, feare
01.01.2015 aa Hr. eat we (are) Eta / rsh / 1 (2010 Fears 09.04.2016 & aga aartiara Feu am
PETROLEUM AND NATURAL GAS REGULATORY BOARD
NOTIFICATION
New Delhi, the 24th November, 2016
F. No. M(1)/T4S/CGD/1/2010.—In exercise of the powers conferred by section 61 of the Petroleum and
Natural Gas Regulatory Board Act, 2006 (19 of 2006), the Petroleum and Natural Gas Regulatory Board hereby makes
the following regulations to amend the Petroleum and Natural Gas Regulatory Board (Technical Standards and
Specifications including Safety Standards for City or Local Natural Gas Distribution Networks) Regulations, 2008,
namely:-
1. Short title and commencement.
(1) These regulations may be called the Petroleum and Natural Gas Regulatory Board (Technical Standards and
Specifications in ing Safety Standards for City or Local Natural Gas Distribution Networks) Amendment
Regulations, 2016.
(2) They shall come into force on the date of their publication in the Official Gazette.
2. In the Petroleum and Natural Gas Regulatory Board (Technical Standards and Specifications including Safety
Standards for City or Local Natural Gas Distribution Networks) Regulations, 2008, -
(i) in Appendix I, serial number 6, under the heading “Critical infrastructure/ activity/ processes”, for “Steel
reinforced rubber hose conforming to IS 9573 Type IV.”, the following shall be substituted, namely: -
“Steel reinforced rubber hose conforming to IS 9573 Type II.”;
ai) in Appendix I, serial number 9, under the heading “Critical infrastructure/ activity/ processes”, for the words
beginning with “Emergency Response Plan, Disaster Management Plan and written emergency procedures...”
and ending with “...material safety data sheets etc. at its disposal.”, the following shall be substituted, namely:-
“Emergency Response Plan, Disaster Management Plan and written emergency procedures. Also, provide for an
Emergency Control Room, manned round the clock and equipped with effective communication system and
emergency vehicles equipped or provided with communication facilities, first aid equipment, fire extinguishers
gas detectors, repair kits and tools, maps, plans, material safety data sheets etc. at its disposal.”;
(iii) in Schedule 1A, under the heading “Pipes and tubing for above ground service lines up to meter set assembly”,
after the words beginning with “The use of copper tubing shall only be after consumer meter such that...” and
ending with “....this is not accessible to third party.” , the following shall be added, namely: -
“Use of copper pipe / tube before consumer meter should be inside the kitchen only.”;
(iv) in Schedule 1A, under the heading “Plastic Pipe and Components”, for the words beginning with “Polyethylene
(PE) pipes conforming to IS 14885 or ISO 4437,....” and ending with “....and PE fittings conforming to ISO
8085 Part 3 shall be acceptable.’’. the following shall be substituted, namely: -
“Polyethylene (PE) pipes conforming to IS 14885 or ISO 4437 and PE fittings conforming to ISO 4437 Part 3 or
EN 1555 Part 3 shall be acceptable.”;
6 THE GAZETTE OF INDIA : EXTRAORDINARY [PART III—SEc. 4]
(vi)
(vii)
(vii)
(ix)
(x)
(xi)
(xii)
(xiii)
(xiv)
in Schedule JA. the heading “Reuse of Ductile Iron Pipes”. and the words under it beginning with “Reuse of
shall be omitted:
ductile...” and ending with “....iron pipes is not permitted.”
in Schedule 1C, under the heading “Fittings other than Valves and Flanges”, for the words “Thermoplastic
fittings conforming to ISO 8085 Part 3 shall be acceptable and shall meet following requirements:”, the following
shall be substituted, namely:-
“Thermoplastic fittings conforming to ISO 4437 Part 3 or EN 1555 Part 3 shall be acceptable and shall meet
following requirements:”:
in Schedule 1C. under the heading “Fittings other than Valves and Flanges”, in sub-paragraph b., the words
“Heating element shall not be exposed and all coils are embedded into the body of the fittings.” shall be omitted:
in Schedule 1D, under the heading “CGD network Description”, in the serial numbers iv) and v), the words
beginning with “(stream redundancy shall...” and ending with, “...not be less than 2+1) ” shall be omitted;
in Schedule 1D, under the sub-heading “Plastic Pipe and Tubing Design Formula”, for the words beginning with
-shall be calculated as per following formula:”, ominal wall thickness of plastic pipe...” and ending with “
the following shall be substituted, namely:-
“The design pressure for plastic gas piping systems or the nominal wall thickness for a given design pressure
shall be determined by the following formula
in Schedule 1D, under the heading “Design Pressure of Plastic Fitting”. for the words beginning with “All PE
fittings shall...” and ending with “...conform to ISO 8085 —Part 3.”, the following shall be substituted. namely:-
“All PE fittings shall conform to ISO 4437 Part 3 or EN 1555 Part 3.7:
in Schedule 1D, under the heading “Plastic Pipe and Tubing Joints and Connections”, under the sub-heading
“General Provisions”, the words beginning with “Fusion fittings shall have inbuilt...
“...beyond external clamp system.” shall be omitted;
and ending with
in Schedule 1D, in the sub-heading beginning with “Control and Limiting of Gas Pressure in High Pressure
Steel...” and ending with *....Ductile iron, Cast Iron or Plastic Distribution system.”, the following shall be
substituted, namely:-
“Control and Limiting of Gas Pressure in High Pressure Steel or PE Distribution System.”;
in Schedule 1D, under the sub-heading, “Control and Limiting of Gas Pressure in low Pressure Distribution
Systems”, the words beginning with “Control and limiting of pressure of gas delivered to domestic, small
commercial,...” and ending with “....and small industrial consumers from high — pressure distribution system.”
shall be omitted ;
in Schedule 1D, under the heading “GAS SERVICE LINES”
Lines”, at the end of the paragraph beginning with “All pla:
provided in confined space.”, the following shall be added, namely:-
, for the sub-heading, “Installation of Service
* and ending with, *...shall be ic pipe and fittings...
“The depth of cover can be further reduced upto 375 mm provided it meets the following requirements:
i. The line pressure shall not exceed 110 mbar.
ii. The diameter of pipe shall not exceed 63mm.
iii. Pipe shall be laid in a trench with Reinforced Cement Concrete (RCC) slab at the top and bottom. The
RCC slab of the roof of basement shall be treated as the bottom.
iv. There shall be a sand filling across three sides of the line pipe of 100 mm each.
v. RCC on top shall have minimum thickness of 150mm.
Vi The top side shall be covered by warning mat.
vii. The Quantitative Risk Assessment (QRA) of the site shall be carried out and specific approval from
management shall be taken for reducing the depth of cover upto 375mm.
viii. The site shall be private property i.e. multi-storey buildings / apartments with no movement of heavy
vehicles.”:
(1 Wi-ws 4)
(xv)
(xvi)
(xvii)
(xviil)
(xix)
(xx)
(xxi)
(xxii)
(xxiii)
(xxiv)
in Schedule 1E, for the sub-headin
of methods...” and ending with “...described in ASME B 31.8, Appendix M can be adopted based on their
effectiveness for the specific areas.”, the following shall be substituted. namely:-
“Any one or combination of methods described in ASME B31.8 can be adopted based on their effectiveness for
the specific areas.”;
in Schedule 1E, for the sub-heading “Repair of Plastic Pipe or Tubing”, for the words beginning with “Only
repair method allowed is use of full encirclement...” and ending with “...split sleeves which shall be in
accordance with ASME B 31.8.*, the following shall be substituted, namely:-
“Repair of Plastic Pipe or Tubing shall be in accordance with ASME B31.8.”;
in Annexure I, under the heading “List of Specifications of Piping Materials used in CGD Network”, in the sub-
heading “Valves”, for the words beginning with “BS 5352...” and ending with “...petrochemical and allied
industries”, the following shall be substituted. namely:-
“BS EN ISO 15761: Steel gate, globe and check valves for sizes DN 100 and smaller, for the petroleum and
natural gas industries
in Annexure I, under the heading “List of Specifications of Piping Materials used in CGD Network”, in the sub-
heading “Valves”, for the words beginning with “BS 5351....” and ending with “...Small Floating ball valve”,
the following shall be substituted, namely:-
“BS EN ISO 17292: Metal ball valves for the petroleum, petrochemical and allied industries.”;
in Annexure I, under the heading “List of Specifications of Piping Materials used in CGD Network”, under the
sub-heading “Fittings”, for the words beginning with “IS 1239 (PART-2)....” and ending with “...and other
wrought steel pipe fittings”, the following shall be substituted, namely:-
“IS 1239 (Part-2): Steel Tubes, Tubular and Other Steel Fittings-Specification-Part 2: Steel pipe fittings.”;
in Annexure I, under the heading “List of Specifications of Piping Materials used in CGD Network”, under the
sub-heading “Plastic Valves”, for the words beginning with “EN 10204....° and ending with *...Excess flow
check valve”, the following shall be substituted. namely:-
“EN 10204: Metallic products- Types of Inspection documents”:
in Annexure I, under the heading “List of Specifications of Piping Materials used in CGD Network”, for the sub-
heading “Brass Fittings”, after the words “IS 319 Free Cutting Leaded Brass Bars, Rods and Sections —
Specification”, the following shall be added, namely:-
“EN 12164: Copper and copper alloys. Rod for free machining purposes.
EN 12165: Copper and copper alloys. Wrought and unwrought forging stock.”;
in Annexure II, under the heading “List of Specifications for Equipment used in CGD Network”, under the sub-
heading “Metering Equipment”, for the words beginning with “OIML R6 / OIML R31....” and ending with
*.,..Diaphragm gas meters”, the following shall be substituted, namely:-
“OIML R 137-1&2: Gas meters.”:
in Annexure II, under the heading “List of Specifications for Equipment used in CGD Network”, under the sub-
heading “Metering Equipment”, the words beginning with “BS 1359 / BS 4161....° and ending with
“...Diaphragm gas meters”, the following shall be substituted. namely:-
“BS 1359 : Gas meters - Diaphragm gas meters.”;
in Annexure II, under the heading “List of Specifications for Equipment used in CGD Network”, under the sub-
heading “Metering Equipment”, the words beginning with “OIML R32....” and ending with “...Rotary piston gas
meters and turbine gas meters” shall be omitted;
8 THE GAZETTE OF INDIA: EXTRAORDINARY [Part HI—Src. 4]
(xxv)
(xxvi)
(xxvil)
in Annexure II, under the heading “List of Specifications for Equipment used in CGD Network”, for the sub-
heading “Electro fusion machine for jointing PE pipe and fittings”. the following shall be substituted. namely:-
“ISO 12176-2: Plastic pipes and fittings- Equipment for fusion jointing polyethylene systems- Part 2:
Electrofusion
EMC Standards
EN-550] 4: Limits and methods of measurement of radio disturbance characteristics of electrical motor
operated and thermal appliances for houschold and similar purposes, electric tools and
similar electric apparatus
EN 61000-6-3: Electromagnetic compatibility (EMC): Generic standards- Emission
standard for residential, commercial and light-industrial environments
EN 61000-6-1: Electromagnetic compatibility (EMC): Generic standards- Immunity for residential,
commercial and light-industrial environments
EN-61000-3-2: Electromagnetic compatibility (EMC): Limits- Limits for harmonic
current emissions (equipment input current < 16 A per phase)
EN-60335-1: Household and similar electrical appliances: Safety- General requirements
EN-60335-2-45: Household and similar electrical appliances: Safety- Particular requirements for portable
heating tools and similar appliances”;
in Annexure IV, under the heading, “Minimum Requirements for GI Pipes and Copper Tubing uscd in service
lines up to consumer appliance”, under the sub-heading “Copper Tubi
use in joining copper tube shall be...” and ending with “...as per BS ED
’, the words beginning with “Fittings for
1254 Parts 1 and 2.” shall be omitted.
in Annexure IV, under the heading, “Minimum Requirements for GI Pipes and Copper Tubing used in service
“Filler e”, for the sub-head 8
nd ending with “...as per BS EN 29453:1994 - So ers alloys - Chemical compositions
and forms.”, the following shall be substituted, namely:-
metals shall
“Filler metals shall be as per BS EN ISO 9453: Electromagnetic compatibility (EMC). Generic Standards.
Immunity for residential, commercial and light industrial environments.”
VANDANA SHARMA. Secy.
[ADVT-IIV4/Exty./316/2016]
Foot Note : Principal regulations were notified vide No. G.S.R. 612(E), dated 27th August, 2008. Amended vide G.S.R.
750(E) dated 14-10-2009. F. No. M(I)/T4S/CGD/1/2010 dated 16-12-2014, F. No. L-MISC/V1/1/2007 dated
01.01.2015 and F. No. M(I)/T4S/CGD/1/2010 dated 09.04.2016.